LV switchgear: functions and selection

  • LV switchgear functions - Electrical protection
  • LV switchgear functions - Isolation
  • LV switchgear functions - Switchgear control
  • Elementary switching devices
  • Combined switchgear elements
  • Switchgear selection
  • Tabulated functional capabilities of LV switchgear
  • Standards and description of circuit-breakers

Fundamental characteristics of a circuit-breaker

  • Other characteristics of a circuit-breaker
  • Selection of a circuit-breaker
  • Coordination between circuit-breakers
  • Selectivity MV/LV in a consumer’s substation
  • Selectivity of Residual Current Devices (RCDs)
  • Maintenance of low voltage switchgear
  • 1 Rated operational voltage (Ue)
  • 2 Rated current (In)
  • 3 Frame-size rating
  • 4 Overload relay trip-current setting (Irth or Ir)
  • 5 Short-circuit relay trip-current setting (Im)
  • 6 Circuit breaker suitable for isolation
  • 7 Rated short-circuit breaking capacity (Icu or Icn)
  • 9 Related technical guides

The fundamental characteristics of a circuit-breaker are:

  • Its rated voltage Ue
  • Its rated current In
  • Its tripping-current-level adjustment ranges for overload protection (Ir [1] or Irth [1] ) and for short-circuit protection (Im) [1]
  • Its short-circuit current breaking rating (Icu for industrial CBs; Icn for domestic-type CBs).

Rated operational voltage (Ue)

This is the voltage at which the circuit-breaker has been designed to operate, in normal (undisturbed) conditions.

Other values of voltage are also assigned to the circuit-breaker, corresponding to disturbed conditions as noted in Other characteristics of a circuit-breaker .

Rated current (In)

This is the maximum value of current that a circuit-breaker, fitted with a specified overcurrent tripping relay, can carry indefinitely at an ambient temperature stated by the manufacturer, without exceeding the specified temperature limits of the current carrying parts.

A circuit-breaker rated at In = 125 A for an ambient temperature of 40°C will be equipped with a suitably calibrated overcurrent tripping relay (set at 125 A). The same circuit-breaker can be used at higher values of ambient temperature however, if suitably “derated”. Thus, the circuit-breaker in an ambient temperature of 50°C could carry only 117 A indefinitely, or again, only 109 A at 60°C, while complying with the specified temperature limit.

Derating a circuit-breaker is achieved therefore, by reducing the trip-current setting of its overload relay, and marking the CB accordingly. The use of an electronic-type of tripping unit, designed to withstand high temperatures, allows circuit-breakers (derated as described) to operate at 60°C (or even at 70°C) ambient.

Note: In for circuit-breakers (in IEC 60947-2) is equal to Iu for switchgear generally, Iu being the rated uninterrupted current.

Frame-size rating

A circuit breaker which can be fitted with overcurrent tripping units of different current level-setting ranges, is assigned a rating which corresponds to the highest current-level-setting tripping unit that can be fitted.

A Compact NSX630N circuit-breaker can be equipped with 11 electronic trip units from 150 A to 630 A. The size of the circuit-breaker is 630A.

Overload relay trip-current setting (Irth or Ir)

Apart from small circuit-breakers which are very easily replaced, industrial circuit-breakers are equipped with removable, i.e. exchangeable, overcurrent-trip relays. Moreover, in order to adapt a circuit-breaker to the requirements of the circuit it controls, and to avoid the need to install over-sized cables, the trip relays are generally adjustable. The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit-breaker will trip. It also represents the maximum current that the circuit-breaker can carry without tripping. That value must be greater than the maximum load current IB, but less than the maximum current permitted in the circuit Iz (see chapter Sizing and protection of conductors ).

The thermal-trip relays are generally adjustable from 0.7 to 1.0 times In, but when electronic devices are used for this duty, the adjustment range is greater; typically 0.4 to 1 times In.

(see Fig. H27 )

A NSX630N circuit-breaker equipped with a 400 A Micrologic 6.3E overcurrent trip relay, set at 0.9, will have a trip-current setting:

Ir = 400 x 0.9 = 360 A

Note: For circuit-breakers equipped with non-adjustable overcurrent-trip relays, Ir = In. Example: for iC60N 20 A circuit-breaker,

Ir = In = 20 A.

Short-circuit relay trip-current setting (Im)

Short-circuit tripping relays (instantaneous or slightly time-delayed) are intended to trip the circuit-breaker rapidly on the occurrence of high values of fault current. Their tripping threshold Im is:

  • Either fixed by standards for domestic type CBs, e.g. IEC 60898, or,
  • Indicated by the manufacturer for industrial type CBs according to related standards, notably IEC 60947-2.

For the latter circuit-breakers there exists a wide variety of tripping devices which allow a user to adapt the protective performance of the circuit-breaker to the particular requirements of a load (see Fig. H28 , Fig. H29 and Fig. H30 ).

  • ^ 50 In in IEC 60898, which is considered to be unrealistically high by most European manufacturers (Schneider Electric = 10 to 14 In).
  • ^ 1 2 For industrial use, IEC standards do not specify values. The above values are given only as being those in common use.

Circuit breaker suitable for isolation

A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard. In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol

All Acti 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category.

Rated short-circuit breaking capacity (Icu or Icn)

The short-circuit current-breaking performance of a LV circuit-breaker is related (approximately) to the cos φ of the fault-current loop. Standard values for this relationship have been established in some standards

The short-circuit current-breaking rating of a CB is the highest (prospective) value of current that the CB is capable of breaking without being damaged. The value of current quoted in the standards is the rms value of the AC component of the fault current, i.e. the DC transient component (which is always present in the worst possible case of short-circuit) is assumed to be zero for calculating the standardized value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is normally given in kA rms.

Icu (rated ultimate s.c. breaking capacity) and Ics (rated service s.c. breaking capacity) are defined in IEC 60947-2 together with a table relating Ics with Icu for different categories of utilization A (instantaneous tripping) and B (time-delayed tripping) as discussed in Other characteristics of a circuit-breaker .

Tests for proving the rated s.c. breaking capacities of CBs are governed by standards, and include:

  • Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit
  • Current and voltage phase displacement. When the current is in phase with the supply voltage (cosφ for the circuit = 1), interruption of the current is easier than that at any other power factor. Breaking a current at low lagging values of cosφ is considerably more difficult to achieve; a zero power-factor circuit being (theoretically) the most onerous case.

In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers.

Figure H31 below extracted from IEC 60947-2 relates standardized values of cos φ to industrial circuit-breakers according to their rated Icu.

  • The dielectric withstand capability
  • The disconnection (isolation) performance and
  • The correct operation of the overload protection have not been impaired by the test.
  • ^ 1 2 3 Current-level setting values which refer to the current-operated thermal and “instantaneous” magnetic tripping devices for over-load and short-circuit protection.

Related technical guides

Download the guide (.pdf)

Combine the benefits of selectivity and cascading to maximize power availability of your LV design at optimized cost.

  • Chapter - LV switchgear: functions and selection
  • Eig-content-pages
  • previous page

About this wiki

The Electrical Installation Guide is now available here as a wiki (Electrical Installation Wiki). This wiki is a collaborative platform, brought to you by Schneider Electric: our experts are continuously improving its content, as they were doing for the guide. Collaboration to this wiki is also open to all.

  • How to browse and search
  • How to contribute
  • Recent changes
  • Special pages
  • Random page

Powered by MediaWiki

  • Switch skin

Home > Protection > Tripping Curves of Circuit Breakers – B, C, D, K and Z Trip Curve

Tripping Curves of Circuit Breakers – B, C, D, K and Z Trip Curve

Types of circuit breaker based on its tripping curve.

A circuit breaker is a protection device employed in every electrical circuit to prevent any potential hazard. There are different types of circuit breakers used all over the world due to their various characteristics & applications. It is necessary to have a circuit breaker that offers adequate protection so that one can work safely around it without having fear of any potential hazards. That is why it is best to know about these kinds of circuit breakers & what kinds of protection do they offer before buying one.

Table of Contents

What is a Circuit Breaker?

A circuit breaker is an electrical device that provides protection against fault current. It breaks the circuit in case of overloading & short circuit. The fault currents generated due to these fault conditions can damage the electrical devices as well as cause fire in a building that can also pose danger to human life.

The circuit breaker instantly cut off the power supply to reduce further damage. A circuit breaker has two types of tripping unit i.e. thermal and magnetic tripping unit.

Thermal Tripping Unit: the thermal tripping unit is used for protection against overloading. It uses a bi-metallic contact that bends with a change in temperature. The current flowing through the bimetallic strip heats up contact & trip the circuit breaker.

The rate of bending of the bi-metallic strip depends on the amount of current. Therefore, greater the overloading current, faster the circuit breaker trips.  

Magnetic Tripping Unit: The magnetic trip unit is used for protection against short circuit current. it includes a solenoid that produced a strong magnetic field due to high short circuit current to instantly trip the circuit breaker.

Related Posts:

  • MCB (Miniature Circuit Breaker) – Construction, Working, Types & Applications
  • MCCB (Molded Case Circuit Breaker) – Construction, Types & Working

trip current meaning

What is a Trip Curve?

A trip curve also known as a current time graph is a graphical representation of the response of a circuit breaker. It shows the current relationship with the tripping time of a protection device.

Why We Need Different Tripping Curves?

Circuit breakers are used for tripping the power supply as quickly as possible in case of overcurrent. But it should not trip so fast & unnecessary that it becomes a problem.

The overcurrent can happen under normal conditions such as the inrush current of a motor. Inrush current is the huge current draw during the starting of a motor that causes voltage dips in the main line. The circuit breaker should be able to tolerate the inrush current & it should provide some delay before tripping.

Therefore, the circuit breaker selected should not trip so fast that it creates a nuisance & it should not trip so late that it causes any damage. This is where the tripping characteristics of the circuit breakers come into play.

The tripping curve tells how fast a circuit breaker will trip at a specific current. The different tripping curves classify the circuit breakers into categories where each category is used for specific types of loads. It is essential to select a circuit breaker that provides the necessary overcurrent protection.

  • Types of Circuit Breakers – Working and Applications
  • Air Circuit Breaker (ACB): Construction, Operation, Types and Uses

How to read a Trip Curve?

The following figure shows a chart of a trip curve.

The horizontal X-axis represents the multiples of the current flowing through the circuit breaker. While the Y-axis represents the tripping time of the circuit breaker on a logarithmic scale.

Tripping Curve

The thermal region shows the response of the bimetallic contact trip unit during overcurrent. The curve shows that the circuit breaker’s tripping time reduces with an increase in the current. The first curve in the graph shows the response of a thermal trip unit.

While the magnetic region shows the response of the solenoid to fault current such as a short circuit current.

As seen from the graph, a circuit breaker does not have a fixed tripping time and we cannot predict an exact tripping point. It is because the tripping is affected by ambient conditions such as temperature. Think of it as a Schrödinger’s Cat area, we do not know when the tripping will occur unless the event happens. 

Types of Circuit Breaker Based on Tripping Curves

The circuit breakers are classified into the following five types based on their tripping curves.

Tripping Curve of Circuit Breakers

Such type of circuit breaker is designed to instantly trip when the operating current is 3 to 5 times its rated current. Their tripping time falls between 0.04 to 13 seconds. They are suitable for domestic applications where surges are very low such as lighting & resistive loads.

Type B Trip Curve

They are sensitive and must not be used in places where the normal surges keep on tripping it unnecessarily.

Type C circuit breaker trips instantly at current surges 5 to 10 times its rated current. its tripping time lies between 0.04 to 5 seconds. As they can tolerate higher surge currents, they are used in commercial applications such as the protection of small motors, transformers, etc.

Type C Trip Curve

Type D circuit breaker trips instantly when operating current reaches 10 to 20 times its rated current. Its tripping time is 0.04 to 3 seconds. Such circuit breakers can tolerate the high inrush current of large motors. Therefore, they are suitable for running heavy loads in industrial applications.

Type D Trip Curve

Such type of circuit breakers trips at 10 to 12 times its rated current with a tripping time of 0.04 to 5 seconds. These circuit breakers are also used for heavy inductive loads in industrial applications.

Type K Trip Curve

Type Z circuit breakers are the most sensitive circuit breaker that instantly trips when the operating current reaches 2 to 3 times its rated current. They are used for sensitive equipment that requires very low short circuit trip settings. 

Type Z Trip Curve

  • Main Difference between Fuse and Circuit Breaker
  • Difference Between MCB, MCCB, ELCB and RCB, RCD or RCCB Circuit Breakers
  • How to Read MCB Nameplate Data printed on it?
  • How to Find the Proper Size of Circuit Breaker? Breaker Calculator and Examples
  • HVDC Circuit Breaker – Types, Working and Applications
  • Can We Use AC Circuit Breaker for DC Circuit and Vice Versa?
  • Electronic Circuit Breaker – Schematic and Working
  • Smart WiFi Circuit Breaker – Construction, Installation and Working
  • Why Circuit Breaker Capacity Was Rated in MVA and Now in kA and kV?
  • How to Wire 120V and 240V Main Panel? Breaker Box Installation – US – NEC
  • How to Wire Single-Phase, 230V Consumer Unit (Breaker Box) with RCD? IEC, UK and EU

This Post has been published by WWW.ELECTRICALTECHNOLOGY.ORG.

Electrical Technology

Related articles.

Solar Panel Installation: Step by Step Procedure with calculation and examples

How Many Panels, Batteries, Charge Controller and Inverter Do I Need?

Battery Charging Current and Battery Charging Time formula with 120Ah battery solved examples

How to Calculate the Battery Charging Time & Battery Charging Current – Example

Automatic UPS Inverter System Wiring Diagram (One Live Wire)

Automatic UPS / Inverter Connection Diagram to the Home Panel Board

How to Find The Correct Size of Cable & Wire in NEC, IET and IEC

How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems

Dark Detector Circuit for Automatic Street Light Control using BC547 Transistor and LDR

Automatic Street Light Control Circuit using LDR & Transistor BC 547

Wire Cable Size Calculator-Copper-Aluminum-AWG

Cable and Wire Size Calculator – Copper and Aluminum

One comment.

Do we have to consider the tripping curves for DIY installation?

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Correct Wire Size for 35-Amp Breaker and Outlet

A complete Electrical Engineering portal

Mcb trip curves – b, c, d, k, and z trip curves.

MCB (Miniature circuit breaker) is a re-settable device designed to protect a circuit from short circuits and overcurrents. The trip curve of an MCB (B, C, D, K, and Z curves) tells us about the trip current rating of Miniature Circuit breakers. The trip current rating is the minimum current at which the MCB will trip instantaneously. It is required that the trip current must persist for 0.1s.

What is an MCB trip curve?

Class b trip curve, class c trip curve, class d trip curve, class k trip curve, class z trip curve, class a trip curve, importance of trip curves, trip curves for other circuit breakers.

The MCB trip curves, also known as I-t tripping characteristic consist of two sections viz, overload section and short circuit section. Overload section describes the trip time required for various levels of overload currents and the short circuit section describes the instantaneous trip current level of MCB.

Read More: Miniature Circuit Breaker (MCB) – Principle of operation

MCB Trip Curves

The X-axis of the chart represents multiples of the circuit breaker’s operating current. The Y-axis shows the tripping time, utilizing a logarithmic scale to cover a range from 0.001 seconds to 10,000 seconds (2.77 hours) across different multiples of the operating current.

The Trip Curve consists of three main components:

  • Thermal Trip area: This area of the curve represents the response of the bi-metallic strip, which is designed to handle slower overcurrents, allowing for inrush or startup currents.
  • Magnetic Trip area: This area of the curve illustrates the response of the coil or solenoid, designed to react swiftly to high overcurrents, such as those occurring during a short circuit.
  • Ideal Trip area: This area curve represents the theoretical desired response of the bi-metallic strip. Due to the inherent variability of the bi-metallic strip and fluctuating ambient conditions, it is challenging to accurately predict the exact tripping point.

The MCB with  class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times the rated current. These MCBs are suitable for cable protection.

MCB with class C trip characteristics trips instantaneously when the current flowing through it reaches between 5 to 10 times the rated current. Suitable Domestic and residential applications and electromagnetic starting loads with medium starting currents.

MCB with  class D  trip characteristics trips instantaneously when the current flowing through it reaches between Above 10(excluding 10) to 20 times the rated current. Suitable for inductive and motor loads with high starting currents.

MCB with class K trip characteristics trips instantaneously when the current flowing through it reaches between 8 to 12 times the rated current. Suitable for inductive and motor loads with high inrush currents.

MCB with class Z  trip characteristics trips instantaneously when the current flowing through it reaches between 2 to 3 times the rated current. These types of MCBs are highly sensitive to short circuits and are used for the protection of highly sensitive devices such as semiconductor devices.

MCB with class A  trip characteristics trips instantaneously when the current flowing through it reaches between 2 to 3 times the rated current. Like Class Z MCBs, these are also highly sensitive to short circuits and are used for the protection of semiconductor devices.

Class B and Class C MCBs are the most commonly used ones. Class C MCBs are used in the lighting power distribution boards in residential and commercial buildings. It trips as soon as the current rises between 5 to 10 times its rated current. Class B MCBs are used in the protection of electronic devices such as PLC, DC power supplies, etc. in control panels. It trips as soon as the current rises between 3 to 5 times its rated current.

In some applications, frequent current peaks occur for a very short period (100ms to 2s). For such applications, class Z-type MCBs shall be used. Class Z-type MCBs are used in circuits with semiconductor devices.

It is important to choose an appropriate MCB current rating and trip curve to safeguard the circuit from damage during faults. Hence it is necessary to calculate the short circuit current and i0nrush current before choosing an appropriate MCB rating. If the chosen MCB rating is much higher than required, then it may not trip in the event of a fault. Similarly, if the MCB is underrated, then it may cause nuisance trips, for example, even the starting currents or inrush currents may trip the MCB.

External selection tool: https://new.abb.com/low-voltage/solutions/selectivity/tools-support/curves

All circuit breakers, such as MCCB, ACB, VCB, etc have their trip characteristics. The only thing is that may not follow the categorization as that of MCB. Also, the circuit breaker curve types are not the same for all types of circuit breakers. It varies from one circuit breaker type to the other and depends on many design factors.

Learn more about MCB:

  • What is an MCB?
  • Miniature Circuit Breaker (MCB) – Principle of operation
  • What is kA rating of MCB and MCCB?

Related Articles: 1.  Difference between MCB and MCCB 2.  Difference between contactors and relays 3.  Difference between Soft Starters and VFDs 4.  Difference between MCCB and RCCB 5.  Difference between MCB and RCBO 6.  Difference between RCCB and RCBO 7.  Difference between MPCB and MCCB

This Post Has 29 Comments

trip current meaning

Very good explanation. I understood the concept. Thank you.

trip current meaning

Thank you, Mr. Sanket. Kindly browse through our articles. Please subscribe or follow us on twitter/facebook for instant updates.

trip current meaning

Thankhs google team good explace thanks again

trip current meaning

Very good mcb make , what Amps load trip make

trip current meaning

Very good. Nice explain.. Good job

trip current meaning

Explanation is good but your second paragraph doesn’t match the charts. It looks like it is the B-curve that trips between 3-5 times its rated current, and C-curve that trips between 5-10 times its rated current.

trip current meaning

Very good, thanks

trip current meaning

very good …..thanks

trip current meaning

Thanks very much

trip current meaning

Very good explanation

trip current meaning

Is this curves is applicable to Rccb ?

No. These curves are applicable for mcbs only.

trip current meaning

Thanks for your information

trip current meaning

The information about mcb is very useful and helpful for a technician, many many thanks for sharing your information.

trip current meaning

Great information, I got to know a few more details out of what I wanted to know.

trip current meaning

Which type is better choice for UPS protection?

trip current meaning

The explanations are very good but in the video is a mistake at minute 0.38. The short circuit sections with the overload section are reversed.

trip current meaning

Good for selection of MCB’s

trip current meaning

On the c type Mcb on the time curves at a short circuit fault current at 220amp it shows dis connection at 6/7seconds are you saying that disconnection will be instant at this current or 6/7 seconds.

trip current meaning

I use B-curve in my home when short circuit occured in the appliace MCB tripped but my appliance burned. My appliance lead wires were shorted by a metal piece was lying on it.I thought MCB could have protected but not. And I also headed big noise of it.

trip current meaning

Sorry to hear that. This could be because the MCB was oversized: Much higher than the rated current of the appliance or the MCB could be faulty. We suggest you replace it with a new one. Make sure that you are choosing the right one.

trip current meaning

Thanks for sharing such an informative article about MCB.

trip current meaning

sir Type C is used for average current load. Type B and C are the most commonly used in DBs. Tripping of MCB Type C is 5-10 times higher than normal.  eg: if a 6A mcb put in acircuit , the rated current is 6 A , then how ever the type c mcb with stand 5 to 10 times higherr than normal .

trip current meaning

hello, what about the CL curve mcb, because in my home installation I used the cl4 code on the mcb

Perhaps you are referring to product name of the MCB and not its trip curve.

trip current meaning

The information is quite educative. Thank you so much

trip current meaning

GOOD INFORMATION

trip current meaning

Leave a Reply Cancel reply

  • Join Insider

Why Do Circuit Breakers Trip?

Master electrician Heath Eastman shows host Kevin O’Connor everything he needs to know about why and how breakers trip.

Heath Eastman talks about circuit breakers. Heath shows Kevin O’Connor that while resetting these breakers is simple, these are complex devices that monitor and protect circuits. First, the two talk about the different sizes of breakers before moving on to the different types. Finally, Heath shows Kevin how to test certain breakers to ensure they’re working properly.

Circuit breakers exist to protect people, appliances, and homes from dangerous electrical current. However, few people understand why the trip and how they operate. Master electrician Heath Eastman shows host Kevin O’Connor why this happens, and even explains a few different types of breakers.

All About Electrical Systems

Breakers Protect Circuits

When electricity comes into the house, it flows through the electrical service panel. From there, the electricity flows out through different branches in the house, each controlled by a circuit breaker. Should a branch begin to overload and overheat, the breaker will trip to prevent damage.

Breaker Sizes

There are two main sizes of breakers in a house: 15 amp and 20 amp. The amp rating explains how much current the breaker can handle before it will trip, and each requires a certain size of wire. Fifteen-amp breakers require a 14-gauge wire, while 20-amp breakers require a 12-gauge wire.

How They Work

A 15-amp breaker won’t necessarily trip the moment it experiences a spike above 15 amps. Many devices draw more amps upon start-up, and these breakers allow those temporary spikes. However, should the breaker sense elevated amperage for longer than is typical, it will trip to prevent the circuit from overheating.

GFCIs and AFCIs

Beyond circuit overload protection, there are other types of breakers that offer additional coverage. These include GFCI breakers and relatively-new AFCI breakers .

GFCI (ground fault circuit interrupter) breakers need to experience the same amount of current going out as coming back through the circuit. If the breaker experiences a drop in returning current, it assumes that the circuit is leaking, whether it be through a water source or a person. When this imbalance occurs, the GFCI trips immediately.

AFCI (arc fault circuit interrupter) breakers sense when the circuit, a device, or an appliance is arcing (the current is jumping from the circuit and onto something else or someone). When the breaker recognizes the arc signature, it trips immediately. These breakers are relatively new and look similar to GFCI breakers, but they’re becoming a code requirement in most locations.

How to Test Breakers

Homeowners, electricians, and inspectors can test their breakers. There are devices that users can plug into an outlet and replicate an error. These devices, known as AFCI/GFCI testers, can trip the breaker altogether or replicate a ground or arc fault, triggering the breaker. This is one of the best ways to ensure that a breaker is working properly.

When to Call a Professional

If a circuit is continuously tripping, or you know that it should be tripping and isn’t, be sure to call in a professional. An electrician will be able to determine the cause of the issue and make sure your circuit breakers and electrical system are safe.

Heath explains what a circuit breaker is, why they trip and how it protects a home. A circuit breaker is a device, installed in the electrical panel, that controls whether power can be sent from the panel through a circuit. Heath explains this ability is controlled by a switch that can be operated either manually—like when a person wants to interrupt power for service—or automatically, like a breaker trip.

He says power overloads, current “leaks”, and arcs are the three reasons that would cause a breaker to trip. A Power overload happens when a device is calling for more power than a receptacle , or a circuit is designed to provide. Current “leaks” are caused when current strays from the circuit for whatever reason, though it happens most commonly when moisture is present. Arcs can happen when the wire breaks down over time (due to overloads but also due to other factors, like animals chewing the wire and other decay) but what Heath sees the most is human error.

If a specific receptacle is consistently tripping the breaker, Heath advises to have a licensed electrician identify the problem to ensure the work is done safely.

Next Up In Electrical

  • How Effective Are Surge Protectors?
  • All About Multimeters
  • How to Label a Circuit Breaker
  • Simple Guide for Selecting a Home Generator
  • All About Portable Power Stations
  • Simple Guide to Installing a Generator Hook-Up

Get the latest This Old House news, trusted tips, tricks, and DIY Smarts projects from our experts–straight to your inbox.

benitezelectricinc

Understanding Trip Circuit: Breakers, Overloads, and Solutions for Short Circuits

Understanding circuit breakers and how to deal with constant tripping.

When the circuit breaker in your home trips, it’s important to reset it in the fusebox to restore power. This may require a trip under the stairs or down to the garage, depending on where your circuit breaker is located. Circuit breakers are designed to interrupt the electrical current when the switch is tripped, ensuring the safety of your electrical system.

While circuit breakers are essential safety devices, constant tripping and repeated resetting can be frustrating. However, if you can identify the cause of the frequent trips, you can take steps to address the issue.

What is a Circuit Breaker?

Every home and business premises have electrical circuits controlled and protected by a switching device located in a consumer unit or fuse panel. Modern systems typically use circuit breakers for control and protection, while older systems might still rely on fuses that blow when overloaded. The main purpose of a circuit breaker is to cut off the flow of electricity to prevent circuits from overheating, which can cause damage and even lead to electrical fires.

How Does a Circuit Breaker Work?

A circuit breaker is a switching device that can be operated manually or automatically. It trips and disconnects the circuit to cut off the electricity supply if there’s an excessive current flow or an overload that the switch can’t handle. The circuit breaker is designed to protect your electrical power system and any devices connected to it.

Why Does a Circuit Breaker Trip?

A circuit breaker will trip when there is an electrical fault that could damage the circuit. This fault typically falls into three categories:

  • Overloads: The most common reason for circuit breakers to trip is overloading. This occurs when you draw more electrical power from a circuit than it can handle. For example, running multiple appliances simultaneously or exceeding the circuit’s capacity. When a circuit overheats due to an overload, it puts all connected appliances at risk. The circuit breaker ensures the wires don’t excessively heat up and protects against fire hazards.
  • Power Surges: Power surges can also cause circuit breakers to trip. These surges happen when there is a sudden increase in electrical voltage, often caused by lightning strikes or faulty wiring in the electrical system. Circuit breakers act as a defense mechanism against power surges by cutting off the excessive flow of electricity.
  • Faulty Components: Another reason for circuit breakers to trip is faulty components within the electrical system. This can include damaged wires, short circuits, or defective appliances. When these faults occur, the circuit breaker detects the problem and interrupts the current flow to prevent damage.

Dealing with Constant Tripping

If your circuit breaker is frequently tripping, it indicates that you are demanding too much power from the circuit. To resolve this issue:

  • Redistribute Appliances: Distribute your appliances and devices onto different circuits. Avoid overloading a single circuit by spreading the load across multiple ones. This ensures that each circuit operates within its designed capacity.
  • Upgrade Your Electrical System: If your system doesn’t have enough circuits to meet modern demands, consider upgrading your electrical system. This may involve installing additional circuits or replacing outdated wiring and panels. A professional electrician can assess your needs and recommend the best solution.

By understanding how circuit breakers work and taking appropriate measures, you can prevent constant tripping, protect your electrical system, and ensure the safety of your home or business.

Understanding Circuit Breaker Tripping: Short Circuits and Ground Fault Surges

Have you ever experienced a sudden power outage in your home or office? Chances are, it was due to a circuit breaker tripping. Understanding the causes of circuit breaker tripping, such as short circuits and ground fault surges, is crucial for ensuring the safety of your electrical system. Let’s explore these common issues in more detail:

1. Short Circuits

Short circuits are a common reason for circuit breaker tripping and should be taken seriously due to their potential danger. A short circuit occurs when a live wire comes into contact with a neutral wire, resulting in an abnormal electrical connection. This can happen in electrical outlets or due to faulty wiring in appliances or plugs.

When a short circuit occurs, the normal electrical resistance is overridden, causing an excessive flow of current through the circuit. This generates excessive heat, which can lead to fires. If you notice a burning smell or dark discoloration around the circuit breaker, it is an indication of a short circuit.

2. Ground Fault Surges

Similar to short circuits, ground fault surges involve a live wire touching a bare copper ground wire or a part of a metal outlet box connected to the ground wire. When this happens, an excess flow of electricity occurs, triggering the circuit breaker to trip. Discoloration around the outlet is also a visible sign of a ground fault surge.

Both short circuits and ground fault surges are not only inconvenient but also pose serious risks to your safety. If your circuit breakers frequently trip, it is crucial to seek professional assistance to identify and resolve the underlying electrical issues. Attempting to solve electrical problems on your own can lead to further complications and put your premises at risk.

Remember, the safety of your electrical system should be entrusted to trained professionals. Don’t hesitate to call for professional help to ensure the proper functioning and safety of your electrical circuits.

Leave a Comment Cancel Reply

Your email address will not be published. Required fields are marked *

Save my name, email, and website in this browser for the next time I comment.

Buell Electric Dunedin FL

1335 Martin Luther King Jr Ave

Dunedin, fl 34698, (727) 648-6101.

Buell Electric

1335 Martin Luther King Jr Ave, Dunedin, FL 34698

CALL US:   (727) 648-6101

Buell Electric

What Does a Circuit Breaker Tripping Mean?

 when there's a circuit breaker tripping, it can indicate that the circuit breaker detects an electrical issue, and it shouldn't be ignored..

circuit breaker tripping

The pandemic-induced surge in home electricity use is real. Consider that, according to the National Bureau of Economic Research, American spending on  home power consump tion  skyrocketed by $6 billion! 

With more usage comes more problems, and circuit breaker issues are among the most common. When there's a circuit breaker tripping, it can indicate that the circuit breaker detects an electrical issue, and it shouldn't be ignored.

 Circuit Breaker Tripping 101

Most circuit breaker issues center around circuit overload. Circuit breakers are a vital part of your home's electrical system since they are designed to prevent costly and damaging surges in electrical current. 

The breaker, working in tandem with a fuse, serves as an electrical unit's internal sensing mechanism. At the slightest sense of excess current, the circuit breaker will "trip," triggering a cease in all electrical activity within the circuit.

Not only can such a smart mechanism help with preventing damage to wires and other electrical components, but circuit breakers can also save lives by preventing electrical fires. According to the National Fire Protection Association,  electrical failures  were the second leading cause of home fires between 2012-2016.

So why do circuit breakers trip? Here are the three most common reasons for circuit breaker tripping and how you can go about fixing a circuit breaker.

 1) Circuit Overload

By far, the m ost common reason a circuit trips is because it's overloaded. Even running a circuit at its electrical capacity can cause home appliances to burn out or a circuit to trip. Ideally, you want to run a circuit below its capacity to keep it from tripping and to prevent any damage from occurring. 

The most familiar example of circuit overload is an over-stuffed power outlet. When you have a dozen gadgets all demanding electrical current to work, eventually that single outlet's capacity will experience overload, and the circuit will trip.

Knowing what each electrical outlet in your house can handle is key to preventing circuit overload. Even a single high-current appliance like a washing machine cannot plug into just any outlet.  Understanding your power outlets  is critical for a safer home.

Before you head to your circuit breaker box or call your electrician, notice what was plugged in at the outlet where the tripped circuit occurred. You may have overloaded it.

 2) Short Circuit

Similar to an overload, when a circuit "shorts," it responds to more current than it can bear. But a short circuit is far more dangerous. 

A short circuit occurs when a "hot" or active wire comes into contact with either another active wire or a neutral wire. The touching wires cause a spike in current that can likewise trip your circuit breaker. Most often, the causes for short circuits are mechanical issues like: 

  • Loose Connections
  • Improper Wiring
  • Damaged Wires

Faulty components, like switches, plugs, cords, appliances, or lighting fixtures, are often culprits of short circuits. Short circuits can occur if you screw or nail into drywall and penetrate an electrical wire.

Remember that short circuits may involve faulty circuit wiring, but the device you're plugging in can cause the problem as well. Keep this in mind, especially if you're using older devices or gadgets that have been out of commission for years, as these can be more prone to short circuits, independent of what's going on in the outlet.

Due to their volatile nature, short circuits are some of the biggest causes of electrical fires, so be extra attentive and don't hesitate to call a professional. As a general rule, most people should never  DIY electrical issues  in their homes.

 3) Ground Fault Surge

 Ground fault surges are similar to short circuits because they involve a sudden spike in current, creating an overload. Ground faults occur when an active wire comes into contact with the ground wire. The contact can come directly or indirectly via the metal housing that connects to the ground wire. 

Copper grounding wires are especially prone to ground fault surges. Copper is the most  conductive material  in everyday use when it comes to home electrical systems. When a hot wire touches the ground wire's copper coating, it results in superconductivity that overwhelms the circuit. A similar result can come from an active wire touching a ground's metal outlet box. 

 Understanding and Fixing Circuit Breaker Issues

So how should you go about troubleshooting a circuit breaker issue? Even though you should leave anything remotely technical to a professional, there are a few things you can do to investigate circuit breaker trip meaning.

First thing's first. Make sure you and your family are safe. Check for signs of excess heat or burning—smell for what could be smoke from an electrical fire. If you sense any signs of a fire, evacuate and call 911.

Check for any discoloration around an outlet. Also, make a note of any sparks or popping noises coming from the outlet. Any of these could be a sign of a ground fault surge or a short, in which case simply flipping the circuit breaker switch won't help. And remember, the older the outlet, the more likely it is to experience problems.

Look for any signs of damage to your devices. Remember that the problem could be coming, not from your home's outlet, but from what you plugged in.

If there are no signs of a blown circuit, try going to your circuit breaker service panel. You may be familiar with this metal box, often located in a garage or utility room. Flip the switch of the house area that tripped, and see if that "resets" the circuit. 

 Fixing a Circuit Breaker

If a simple flipping of the switch doesn't work, it's time to call a professional electrician. The seasoned team at Buell Electric can assess the problem and fix a circuit breaker, which may involve repairs or upgrades. 

Circuit breaker tripping may be as innocent as overloading an outlet, but it can point to more serious problems as well. The best way to know for sure is to  contact us  today.

Newer Post >

Buell Electric's Blog

Tampa Hurricane Electrical safety

Electrical Safety Tips for Hurricane Season in Tampa

Commercial electrical services

Protect Your Business with Professional Commercial Electrical Services

home electrician tampa

Shedding Light on Your Home: Finding the Right Electrician in Tampa

changing technology

How Electricians Keep Up with Changing Technology in the Industry

electrical maintenance services

The Importance of Regular Electrical Maintenance For Your Business

marine electrical standards

Marine Electrical Standards and Regulations You Need to Know

smart home system

The Benefits of Installing a Smart Home System

electrical wiring

Understanding the Different Types of Electrical Wiring in Your Home

electrical emergency

How to Prepare Your Home for an Electrical Emergency

ceiling fan installation

5 Reasons Your Ceiling Fan Installation Should be Left to the Pros

Home Advisor Screened and Approved

[email protected]

Mon-fri 9:00 am - 5:00 pm sat-sun 10:00 am - 5:00 pm privacy page, connect with us:.

Buell Electric State Certified Electrical Contractor

Mon-Fri 9:00 AM - 5:00 PM Sat-Sun 10:00 AM - 5:00 PM

All Rights Reserved | Buell Electric, Inc.

trip current meaning

Physics Network

What is a trip switch in physics?

Trip switches are basically fuses; when too much current (AKA load) passes through a given circuit the switch (which are rated e.g. 13 AMP) is ‘tripped’ and the circuit is broken. The trip switches in the picture are all currently switched on.

Table of Contents

What is the main trip switch?

The main switch – Turns off the electricity supply to your home. Useful in an emergency. Fuse switches (or circuit breakers) – Switches that trip to protect the appliances in your home, if there’s a fault in the circuit.

What is the meaning of trip current?

The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit-breaker will trip. It also represents the maximum current that the circuit-breaker can carry without tripping.

Why do trip switches go?

Old, damaged, or faulty electrical appliances can leak extra current, and safety switches will trip when they detect the excess flow. With heavily used appliances, wear and tear is the main reason for performance issues, so you need to maintain them properly. If a switch goes off, first try resetting it.

How do you trip electricity?

  • Plug an appliance into an outlet fed by the circuit that the breaker you want to trip is serving.
  • Open the electrical panel (breaker box) and search for the breaker corresponding to your targeted circuit.
  • Flip the coinciding breaker switch to the “off” position.

How do you tell if a switch is tripped?

YouTube video

How do you make a trip switch?

  • Turn off All Devices on Circuit. Turn off all devices on the electrical circuit.
  • Find Electric Service Panel.
  • Locate Tripped Breaker.
  • Turn Circuit Breaker Handle to off Position.
  • Turn Circuit Breaker Handle to on Position.
  • Test Circuit.

What causes appliances to trip?

Three of the most common reasons why this may happen are: Too many electrical appliances are in use together, which overloads the circuit. One of the electrical appliances in the house is faulty. There is a faulty power connection in one of the appliances.

Why does fuse keep tripping?

When a circuit breaker regularly trips or a fuse repeatedly blows, it is a sign that you are making excessive demands on the circuit and need to move some appliances and devices to other circuits. Or, it may indicate that your house has too few circuits and is in need of a service upgrade.

How does a trip work?

When a trip is activated, the trip mechanism releases the operating mechanism, which opens the contacts. Note: the drawings in this section show an AC power source; however, a DC source could also be used. The operating mechanism is held in the “ON” position by the trip mechanism.

What is a tripping device?

[′trip·iŋ di‚vīs] (electricity) Mechanical or electromagnetic device used to bring a circuit breaker or starter to its off or open position, either when certain abnormal electrical conditions occur or when a catch is actuated manually.

How does a trip unit work?

A trip unit is the part of a circuit breaker that opens the circuit in the event of a thermal overload, short circuit or ground fault. An open circuit will not conduct electricity because either air, or some other insulator has stopped or broken the flow of current in the loop.

How do I test a trip switch?

YouTube video

Why is safety switch tripping?

Reasons your safety switch might trip overloaded power sockets or power boards. faulty appliances. faults your home wiring. water in the walls or ceiling affecting the power circuit – Has it rained recently or is there a sprinkler hitting an outdoor power point?

Why does the earth leakage trip?

An ‘earth leakage trip’ means that an earth leakage current has been detected. This usually indicates there is an issue with the leakage current of the installation or of the vehicle. We advise to contact the installer or operator of the charging station for inspection and possible repair.

How do you fix a trip switch?

YouTube video

How do you trip test a circuit breaker?

YouTube video

Can a circuit breaker fail without tripping?

A circuit breaker can fail without tripping and is an indication it needs to be replaced. It can also mean there are wiring issues with the circuit itself, such as exposed/loose wiring, overheating, and unregulated voltage.

What is a tripped circuit breaker?

When it is said that a circuit breaker “trips,” it means that circuit has detected what’s known as a fault condition and has shut itself off to prevent the wiring from overheating and potentially igniting itself.

How do you fix a tripped fuse?

  • Unplug electrical appliances. First and foremost, it’s important to identify where the outage occurred.
  • Turn the power off. Next, you will need to turn off the main power to the fuse box.
  • Find the fuse box.
  • Identify the broken fuse.
  • Replace the fuse.
  • Test your new setup.

How does a tripped breaker look like?

YouTube video

How does a switch work in a circuit?

An electric switch is a device that interrupts the electron flow in a circuit. Switches are primarily binary devices: either fully on or off and light switches have a simple design. When the switch is turned off, the circuit breaks and the power flow is interrupted. Circuits consist of a source of power and load.

What happens when electricity trips?

Each breaker you see in the panel has an ON/OFF switch and controls a separate electrical circuit in your home. When a breaker trips, its switch automatically flips to the “OFF” position, and it must be manually turned back on in order for electricity to flow through the circuit again.

How does a trip coil work?

Trip coils are the release components in circuit breakers used in energy distribution for the switching of high currents. It is their task to interrupt fault currents/voltages so that downstream systems are not damaged. The trip coil triggering solenoid initiates this separation mechanism.

Why is my fridge tripping the power?

If your refrigerator trips often, then it is likely due to the compressor. Every time your compressor turns on to run the cooling cycle, it will trip the breaker. When this happens, it is typically due to a grounding issue with the compressor that is causing the part to essentially become overloaded with electricity.

Craving More Content?

Read our latest blog posts

What is a special medical radiation physics consultation.

Coding Answer: CPT® code 77370 (Special medical radiation physics consultation) is used when the radiation oncologist makes a direct request to the qualified medical physicist for…

What’s the difference between special and general relativity?

Special relativity applies to all physical phenomena in the absence of gravity. General relativity explains the law of gravitation and its relation to other forces of…

What is slinky wave?

This wave is a movement of motion! This wave is called a transverse wave because the motion of the slinky is sideways to the motion along…

AutomationDirect

Recent Orders

Your account.

Checkout   $0.00

  • Product Returns (RMAs)
  • Pay Proforma Invoices
  • Pay Freights
  • Invoices / Invoice Reprint
  • Quotes / Favs / BOMs
  • Packing List Reprint
  • My Product Docs
  • Credit Application
  • Barcode / RFID / Vision
  • Bulk Wire & Cable
  • Cables (Terminated)
  • Circuit Protection / Fuses / Disconnects
  • Communications
  • Drives & Soft Starters
  • Enclosure Thermal Management & Lights
  • Enclosures & Racks
  • HMI (Human Machine Interface)
  • Hydraulic Components
  • Motion Control
  • Motor Controls
  • Pneumatic Components
  • Power Products (Electrical)
  • Power Transmission (Mechanical)
  • Process Control & Measurement
  • Programmable Controllers
  • Pushbuttons / Switches / Indicators
  • Relays / Timers
  • Sensors / Encoders
  • Stacklights
  • Structural Frames / Rails
  • Tools & Test Equipment
  • Water (Potable) Components
  • Wiring Solutions
  • Retired Products
  • E-newsletter
  • Online PDF Catalog
  • Order Catalog On USB
  • Download Price List
  • Video Tutorials
  • Company Reviews
  • Job Opportunities
  • Product Application Stories
  • Learning Library
  • Affordable Training
  • Free Online PLC training
  • Find an authorized integrator
  • Track Your Order
  • Pay Open Invoices
  • Product Comparison Feature - How To Video
  • Cybersecurity
  • Programmable Logic Controllers
  • Productivity1000 PLCs
  • Productivity2000 PLCs
  • Productivity3000 PLCs
  • ProductivityCODESYS
  • LS Electric XGB Series PLCs
  • ProductivityOpen
  • Do-more H2 PLCs or Do-more T1H Series
  • Do-more BRX PLCs
  • C-more Touch Panels
  • AC & DC Drives
  • PLC Family Selector
  • P1000 PLC Systems
  • P2000 PLC Systems
  • P3000 PLC Systems
  • CLICK PLC Systems
  • Do-more ® BRX PLC Systems
  • LS-Electric ® XGB PLC Systems
  • Productivity ® Open Systems
  • Datalogic ® Safety Light Curtains
  • LS-Electric ® Servo Systems
  • Nitra ® Pneumatic Grippers
  • Object Detection (Sensors)
  • PAL Controller Configurator
  • Precision Gearbox Selector
  • Protos X ® Field I/O
  • Quadritalia ® Modular Enclosures
  • Stellar ® Soft Starters
  • Stepper System Selector
  • SureFrame T-slot Extrusion
  • SureMotion ® XYZ Gantry
  • SureServo2 ® System Selector
  • SureStep ® Linear Actuators
  • Timing Belts & Pulleys
  • Werma ® Stacklights

What is a Trip Curve? Understanding Circuit Breaker Trip Curves From AutomationDirect

BW125JAGU-3P020SB Thumbnail

https://www.AutomationDirect.com/circuit-protection (VID-CP-0009) Circuit breaker and fuse trip curves (CB Trip curves) explain how a trip occurs based on current and time. Example: A Curve B Curve C Curve D Curve

AutomationDirect carries a full selection of industrial circuit protection devices with incredible prices, high stock rates and fast shipping. Trip curves may be called tripping characteristics, current curve, current-time curve or other terms. A trip curve is simply a description of how an overcurrent based on time will trip a fuse or circuit breaker. For this video we’ll focus on breakers but the same applies to fuses. You may see breakers sold based on trip curve. Looking at the curve chart, this axis is time and this one is amperage as a multiple of rated current. It’s obvious at a glance that the lower the current the longer it takes to trip. This is common for most breakers and fuses. The intended use of the device determines the desired curve. This curve has 3 different curves in one chart because the breakers for this chart are available in B, C or D curves. Lets look at the range of typical motor inrush. This is usually 6 – 8 times the motor FLA. We can see on a B or C curve this amount of current would trip the breaker well under .01 seconds. This would not be enough time for a motor to start and the current to come down. But on the D curve this gives us at least 1 second which should be plenty of time for the inrush to subside. So, as you can see D curve breakers are intended of highly inductive loads like motors or transformers. The faster acting B curve is used for resistive loads which have little to no inrush and the C curves are used where only limited inductive loads are present such as lighting or control circuits. Whether you prefer circuit breakers, fuses, disconnect switches or other types of circuit protection, Automation Direct is your common sense way to buy industrial controls. If you need more assistance please see our free tech support options here. We have a vast library of other videos please click here to view all product videos. Click here to subscribe to our YouTube channel for upcoming products and solutions.

Company Information

linkedin

Voted #1 mid-sized employer in Atlanta Check out our job openings

Electrical Engineering Resource

Power circuit breaker ratings explained

Darryl Moser Sales Enablement Manager ABB Electrification Products Division

When selecting the right low voltage power circuit breaker for an application, it is important to consider both short-circuit current ratings and short-time current ratings. Understanding these performance characteristics will help you choose between the various circuit breaker designs.

A circuit breaker is selected based on its electrical ratings to serve a particular purpose in each application, proper selection of the circuit breaker is essential for the safe and correct operation of the electrical system. Two important ratings to consider are; short-circuit current rating (this is commonly referred to as the maximum interrupting rating) and the short-time current rating. In this post, we will discuss these circuit breaker ratings and how they can affect the protection and selective coordination of the system.

Short-circuit current ratings defined

The short-circuit current rating is the maximum short circuit current that the circuit breaker is rated to safely interrupt at a specific maximum voltage. This short-circuit current rating is normally expressed in rms symmetrical amperes and is specified by the current magnitude only. If a circuit breaker is provided with instantaneous phase trip elements, the interrupting capacity is the maximum rating of the device with no intentional delay. If the circuit breaker is provided without instantaneous phase trip elements, or if the instantaneous phase trip elements can be disabled by the user, the interrupting capacity is the maximum rating of the device for the rated time interval. An engineer can safely apply a circuit breaker in a power system where the available short-circuit fault current on the supply side terminals does not exceed its maximum interrupting rating.

Short-time current ratings defined

The short-time current rating of a circuit breaker is the ability of the circuit breaker to withstand the effects of the rated short-time current level over defined time duration. It demonstrates the ability of the breaker to remain closed for a time interval under high fault current conditions. The short-time current rating is used by the engineer to determine the ability of the circuit breaker to protect itself and to coordinate with other circuit breakers so the system will trip selectively.

Switchgear ratings

Users of low-voltage switchgear commonly use the phrase “bus bracing” to refer to the mechanical strength of the bus bar system in the equipment, but when you look into the standards you will not find “bus bracing” defined or listed as a rating. The product standards applicable to Metal-Enclosed Power Circuit Breaker Switchgear are IEEE C37.20.10 for definitions and IEEE C37.20.1-2018 and C37.51- 2018 for the ratings; [1] [2] [4].

“Rated short-circuit withstand current: The maximum rms current that a circuit can carry momentarily without electrical, thermal, or mechanical damage or permanent deformation. The current shall be the rms value, including the dc component, at the major peak of the maximum offset phase as determined from the envelope of the current wave during a given test time interval.” [1]

For ratings, reference IEEE C37.20.1 – 2015, IEEE Standard for Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and below) Power Circuit Breaker Switchgear. [2]

Rated short-circuit withstand current, which is the rated symmetrical short-circuit current that the switchgear bus must be able to withstand for a time duration of at least four electrical cycles, 0.067 seconds on a 60 Hz system. During this test the voltage must be at the maximum rated value such as 635V as opposed to a nominal value of 600V and it must be at a power factor of 15% or lower which translates into a peak current of at least 2.3 times the rms value.

The test to verify rated short-time withstand current in low-voltage metal enclosed switchgear is conducted by applying the short-time current level for two periods of one-half second (30 cycles), separated by a fifteen second interval with no current; or, at the option of the switchgear manufacturer, the test can be performed as a single test of one full second (60 cycles).

Circuit breaker ratings

trip current meaning

The rated short-time current in LVPCBs is a rating given to non-automatic circuit breakers, those without trip units, and for non-fused automatic circuit breakers.

Note: Rated short-time withstand current is not applicable to fused circuit breakers as the fuse will open prematurely and not allow the current to flow for the full duration of the rated short-time withstand test.

emax trip units

Modern electronic trip units allow for maximum time-current curve shaping which helps you to selectively coordinate with other circuit breakers. These trip units are designed with adjustments for long-time pickup threshold and time delay, shorttime pickup threshold and time delay, instantaneous pickup, and ground fault pickup threshold and time delay.

Protection and coordination

Equipment protection and coordination can be competing objectives of the system designer, when applied within their electrical ratings circuit breakers will safely protect both themselves and the electrical system. Selective coordination is necessary when continuity of service is desired. This is often achieved through the use of the circuit breaker’s short-time ratings. An intentional tripping delay may be applied only when downstream circuit breakers have an adequate short-time current rating or are self-protecting.

For many applications in low-voltage power distribution systems, a lesser short-time current rating may be acceptable; but, for applications such as a main circuit breaker in a service entrance switchboard or switchgear, it may not be. A low-voltage power circuit breaker used as a main circuit breaker that has a 65 kA short-time current rating would allow the flexibility to coordinate with downstream circuit breakers for a fault of any magnitude up to the full 65 kA short circuit current rating of the circuit breakers and switchgear.

Proper selection of LVPCBs is critical to the performance of the electrical system. Choosing circuit breakers with an appropriate short-circuit current rating and short-time current rating provides the opportunity to have a selectively coordinated system up to high fault current levels.

Emax 2 Circuit Breaker Ratings

emaxTable

[1] IEEE C37.20.10 – 2016, IEEE Standard Definitions for AC (52 kV and below) and DC (3.2 kV and below) Switchgear Assemblies [2] IEEE C37.20.1 – 2015, IEEE Standard for Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and below) Power Circuit Breaker Switchgear [3] ANSI C37.50 – 2018, Low Voltage AC Power Circuit Breakers Used in Enclosures— Test Procedures [4] ANSI C37.51 – 2018, Metal-Enclosed Low-Voltage AC Power Circuit Breaker Switchgear Assemblies— Conformance Test Procedures [5] UL 1066, Fourth Edition, Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures

Related Content

Check out more on power circuit breakers: Emax 2 circuit breakers on ABB website

Presented by:

trip current meaning

This site is created by ABB application engineers and experts as an educational tool to help engineers.

short circuit current ratings

D & F Liquidators Logo

Understanding Why Your Circuit Breaker Keeps Tripping

circuit breaker tripped with a burn mark

Table of Contents

If you’ve got a circuit breaker that just won’t stay on, you may be dealing with a frustrating and potentially worrisome situation. Circuit breakers play a crucial role in your home’s electrical safety, and a constantly tripping one signals  a problem that needs attention.

This blog is here to help you with the common causes of frequent tripping, how to troubleshoot them, and everything else. Read on to know more!

Table of Content

  • What is a Circuit Breaker?

Why Does My Circuit Breaker Keep Tripping?

  • How to find what is tripping my circuit breaker?

What to Do if Circuit Breaker Still Keeps Tripping?

What is a circuit breaker (and why does it trip).

An electrical circuit breaker is a switching device that can be operated automatically or manually to control and protect the electrical power system and the electrical devices connected to it.

The circuit breaker trips when too much electricity flows through it or when it cannot handle the excess current load. In layman’s terms, this situation is called an electricity trip. It means that the flow of electricity is cut off to keep your circuits from overheating or causing more damage.

If there had been no electric trips, house fires would have been quite common. Read on to learn more about this critical electric safety topic!

If there is frequent tripping in your circuit breaker, it indicates something is going wrong with the circuit. There may be a short circuit in one of your appliances or a ground fault. Maybe there is a circuit overload or a sign indicating the circuit breaker box is faulty. Keep an eye out for all of these reasons, especially if your main breaker keeps tripping .

If you know what causes a circuit breaker to trip , you can take action to prevent it from happening again. Let’s delve into 6 main reasons that cause circuit breakers to trip frequently(and it’s troubleshooting).

Overheating Appliance

Circuit overload.

A circuit overload occurs when you want a particular circuit to provide more electricity than its actual capacity. This leads to overheating the circuit, which puts all the electrical appliances connected to the circuit at risk.

For example, suppose your television is connected to the circuit, which actually needs 15 amps but is now using 20 amps. In that case, the circuit of the television system can get fried and damaged. The circuit breaker trips to prevent this from happening, potentially even preventing a significant fire.

It’s vital to identify the overloaded circuit, switch the tripped breaker back on, and then carefully plug your appliances back in. Try to redistribute your electrical devices and keep them off of the same circuits as recommended by fellow electrical repairmen.

Short Circuits

Another common reason why power keeps tripping is a short circuit . It’s more dangerous than an overloaded circuit. A short circuit is caused when a “hot” wire comes into contact with a “neutral wire” in one of your electrical outlets. When this happens, a large amount of current flows through the circuit, creating more heat than what the circuit can handle.

Ground Fault Surges

Generally, arc faults is also considered to be a major reason behind frequently tripped circuit breakers. An arc fault happens when loose or corroded wires create a short contact that causes an arc or a spark. This creates heat and can risk an electrical fire. If you hear your light switch hissing or the outlet buzzing, you are experiencing an arc fault.

Defective Circuit Breaker

What if you find out that the reasons mentioned above are not why your circuit breaker keeps tripping ? Well, in that case, maybe your circuit breaker is at fault. When the breaker is old and cannot produce electricity anymore, it’s time to replace it. Also, a breaker is bound to wear out if not maintained.

How to Find What is Tripping my Circuit Breaker?

When a circuit breaker trips, it means there is an electrical problem that needs to be addressed. To find out what is causing the breaker to trip, follow these steps:

  • Turn off all the devices and appliances that are connected to the circuit that is tripping the breaker.
  • Reset the circuit breaker by flipping it to the “off” position and then back to the “on” position.
  • Turn on each device one at a time and see if the breaker trips again.
  • If the breaker trips when a specific device is turned on, unplug that device and try plugging it into a different circuit.
  • If the breaker does not trip when the device is plugged into a different circuit, then the problem is likely with the original circuit.
  • If the breaker continues to trip even with all devices and appliances unplugged, the problem may be a short circuit or a faulty breaker.

If you are not comfortable with or qualified to deal with electrical issues, it is best to contact a licensed electrician to diagnose and fix the problem.

If a circuit breaker keeps tripping even after trying the troubleshooting steps mentioned earlier, it’s best to get in touch with an electrician and have them look into it. In the meantime, for your safety, you can also try inspecting it yourself using these methods with appropriate caution.

  • Unplug Devices: Manually switch off any devices and then unplug them. This is necessary because once the power surges back and the devices are still on, it might affect them adversely.
  • Reset the Circuit Box: Go to the circuit breaker and switch it off or remove the fuse. Turn it on again. This is how you reset a circuit breaker .
  • Check the Reasons: Inspect the circuit box again and check whether any of the above reasons tick the current situation of your circuit breaker.
  • Switch on the Devices: You need to test the circuit by switching on all the lights and appliances you unplugged. This gives you an idea of what is causing the breaker to trip.
  • Check or Replace: Once you check all the devices, decide whether you need to replace the circuit breaker with a new one. It is critical to treat electrical issues carefully. If your circuit breaker keeps tripping , it means something isn’t right. Understanding why it is happening frequently and how to diagnose and cure this problem can help you keep your house safe and prevent damage. However, it is always advisable to call a licensed electrician if such issues persist.

Conclusion:

A tripping circuit breaker is a warning sign that something is amiss within your electrical system. Understanding the basics of how circuits work and simple troubleshooting can help you pinpoint easy fixes. As mentioned earlier, electrical issues can be complex. Contact a qualified electrician when dealing with repeated trips.

What is The Purpose of a Circuit Breaker?

How circuit breaker works, what are the signs of a faulty circuit breaker, how to reset circuit breaker, what is the difference between a fuse and a circuit breaker, is it dangerous if the circuit breaker keeps tripping, how do i fix a circuit breaker that keeps tripping, how to tell if a circuit breaker is bad, can i replace a circuit breaker myself.

DFLIQ logo

D&F Liquidators has been serving the electrical construction materials needs for more than 30 years. It is an international clearinghouse, with 180,000 square facility located in Hayward, California. It keeps an extensive inventory of electrical connectors, conduit fitting, circuit breakers, junction boxes, wire cable, safety switches etc. It procures its electrical materials supplies from top-notch companies across the globe. The Company also keeps an extensive inventory of electrical explosion proof products and modern electrical lighting solutions. As it buys materials in bulk, D&F is in a unique position to offer a competitive pricing structure. Besides, it is able to meet the most discerning demands and ship material on the same day.

Share This Story, Choose Your Platform!

Related posts.

How to Ground an Outlet? (Safely!)

How to Ground an Outlet? (Safely!)

What is an Electrical Fuse?

What is an Electrical Fuse?

Understanding Transformer Components (An Essential Guide)

Understanding Transformer Components (An Essential Guide)

What is a GFCI Outlet and How Does It Keep You Safe?

What is a GFCI Outlet and How Does It Keep You Safe?

What’s Causing Buzzing Circuit Breaker Box & How to Fix it?

What’s Causing Buzzing Circuit Breaker Box & How to Fix it?

Get to us…..

1810 W. Winton Avenue Hayward, CA 94545-1232

Phone: (800) 458-9600

Fax: (510) 785-1668

Email: [email protected]

Web: D&F Liquidators

  • Introduction
  • Motor Failure and Protection
  • Protection of Motor Branch-Circuits
  • Withstand Ratings
  • Melting Alloy Overload Relays
  • Automatic Reset
  • Ambient-Temperature Compensated Bimetallic Overload Relays
  • Thermal Overload Relay Trip Characteristics
  • Phase Loss and Phase Unbalance
  • Separate Mounting—Melting Alloy Overload Relays
  • Replacement Melting Alloy Overload Relays for Class 8536 Starters
  • Special Features for Melting Alloy Overload Relays
  • NEMA Style Melting Alloy Overload Relays Dimensions
  • Class 9998 Contact Units
  • Class 9999 Isolated Alarm Contacts
  • Class 9998 Jumper Strap Kits
  • Other Features
  • Class 9065 Motor Logic SSOLR Selection Tables
  • NEMA Style Dimensional Diagrams
  • Isolated Auxiliary Contacts
  • DIN Adapter
  • Lug-Lug and Lug-Extender Kits
  • Remote Reset Module
  • Adapted Bimetallic or SSOLR Mounting Bracket Adapter—NEMA Sizes 00–1
  • TeSys™ D Solid-State Overload Relays for Type S Starters
  • Communication Protocols
  • Protection Functions
  • Meter Functions
  • Motor Control Functions
  • Motor Control Modes
  • Statistical and Diagnostic Functions
  • Standards and Certifications
  • Configuration
  • LTMR Controllers
  • Expansion Module
  • HMI Modules
  • Transformers, Senors, and Probes
  • SoMove™ Software for Configuration
  • Accessories for Connecting the Components
  • Dimensional Diagrams (mm)
  • External Reset Mechanisms — Class 9066
  • Nameplate vs. NEC Full-Load Current
  • Service Factor
  • Motor Branch-Circuit Design
  • Thermal Overload Relays
  • Motor Logic Solid-State Overload Relays
  • Application
  • Procedure for Thermal Unit Selection
  • Selecting Slow Trip Thermal Units
  • Selecting Thermal Units

Procedure for Calculating the Trip Current Rating

  • Calculating the Trip Current for Ambient Temperatures Other than 40 °C
  • Thermal Unit Selection on an Approximate Basis—Based on Horsepower and Voltage
  • Mounting the Thermal Units

For the best experience of this site, please enable Javascript for the www.productinfo.schneider-electric.com domain.

Use the selection table for the specific controller involved.

Find the minimum motor full-load current listed for the thermal unit.

Multiply that current by 1.25 (1.15 for Class 8198). The result is the trip current rating.

Determine the thermal unit selection and trip current rating for thermal units in a Class 8536 Type SCG3 Size 1 magnetic starter used to control a three-phase, 1.15 service factor motor with a full-load current of 17.0 Amperes, where the motor and controller are both located in a 40 o C (104 o F) ambient temperature.

From thermal unit Table 13 , the proper selection is B32.

The minimum motor full-load current is 16. 0 Amperes.

Trip current rating is 16.0 x 1.25= 20.0 Amperes.

Protection Level: Is the relationship between trip current rating and full-load current. Protection level, in percent, is the trip current rating divided by the motor full-load current times 100. In the example above, the protection level for the B32 thermal unit is: 20.0/17.0 x 100=118%.

National Electrical Code, Section 430-32, allows a maximum protection level of 125% for the motor in the above example.

Minimum Trip Current: Also called ultimate current, may vary from the trip current rating value, since ratings are established under standardized test conditions. Factors which influence variations include:

The number of thermal units installed

Enclosure size

Proximity to heat producing devices

Size of conductors installed

Ambient (room) temperature, and others

Except for ambient temperature-compensated overload relays, an ambient temperature higher than 40 o C would lower the trip current, and a lower temperature would increase it. This variation is not a factor in selecting thermal units for the average application, since most motor ratings are based on an ambient temperature of 40 °C, and motor capacity varies with temperature in about the same proportion as the change in trip current. Temperature-compensated relays maintain a nearly constant trip current over a wide range of ambient temperature, and are intended for use where the relay, because of its location, cannot sense changes in the motor ambient temperature.

Show QR code for this page

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?

Contact Information

Legal information.

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions.

This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

© 2019 – 2021 Schneider Electric.

IMAGES

  1. Understanding Trip Curves

    trip current meaning

  2. How To Read A Circuit Breaker Trip Curve

    trip current meaning

  3. IEC60947-4-1 tripping time curves as a function of actual to full-load

    trip current meaning

  4. Actual trip current waveform and parameters.

    trip current meaning

  5. 🔵 Trip Meaning

    trip current meaning

  6. Understanding Trip Curves

    trip current meaning

VIDEO

  1. Trip

  2. Trip Meaning

  3. Kapyong Park: More Than Just a Green Space

  4. #MF-USMF110 ,#PTC Resettable ,#Bourns, #RelaysManufacturers, #InductorsCompany, MobikeChip

  5. Quickie: Argument from Etymology

  6. MIA: The Mount Albert Community Centre Memorial

COMMENTS

  1. Fundamental characteristics of a circuit-breaker

    The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit-breaker will trip. It also represents the maximum current that the circuit-breaker can carry without tripping. That value must be greater than the maximum load current IB, but less than the maximum current permitted in the circuit Iz ...

  2. How circuit breaker trip unit works?

    The trip unit is the part of the circuit breaker that determines when the contacts will open automatically. In a thermal-magnetic circuit breaker, the trip unit includes elements designed to sense the heat resulting from an overload condition and the high current resulting from a short circuit. In addition, some thermal magnetic circuit ...

  3. 6 Adjustable Tripping Settings of a Circuit Breaker You MUST ...

    Continuous current [Amps] Go back to CB tripping settings ↑. 2. Long-Time Delay. Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush currents, such as those encountered when starting a motor, to pass without tripping.. The adjustment is from 2.2 to 27 seconds at six times the continuous amps (Ir) setting.. As shown below, the long-time delay effects ...

  4. The Basics Of Circuit Breaker Tripping Units

    The thermomagnetic trip unit consists of two parts: The thermal trip unit - Made up by a bimetal thermal device which actuates the opening of a circuit breaker with a delay depending on the overcurrent value. This trip unit is intended for the protection against overloads. The magnetic trip unit - Made up by an electromagnetic device, with ...

  5. Tripping Curves of Circuit Breaker. B, C, D, K & Z Trip Curve

    A circuit breaker has two types of tripping unit i.e. thermal and magnetic tripping unit. Thermal Tripping Unit: the thermal tripping unit is used for protection against overloading. It uses a bi-metallic contact that bends with a change in temperature. The current flowing through the bimetallic strip heats up contact & trip the circuit breaker.

  6. MCB Trip Curves

    MCB (Miniature circuit breaker) is a re-settable device designed to protect a circuit from short circuits and overcurrents. The trip curve of an MCB (B, C, D, K, and Z curves) tells us about the trip current rating of Miniature Circuit breakers. The trip current rating is the minimum current at which the MCB will trip instantaneously.

  7. Why Do Circuit Breakers Trip?

    The amp rating explains how much current the breaker can handle before it will trip, and each requires a certain size of wire. Fifteen-amp breakers require a 14-gauge wire, while 20-amp breakers require a 12-gauge wire. How They Work. A 15-amp breaker won't necessarily trip the moment it experiences a spike above 15 amps.

  8. What Causes a Circuit Breaker to Trip?

    Highlights. There are three reasons why a circuit breaker trips: a ground fault surge, a short circuit, or an overloaded circuit. A hot wire crossing with or touching a neutral wire triggers a short circuit, tripping your circuit breaker. If resetting the breaker doesn't solve the problem, consult a licensed electrician.

  9. Understanding Trip Circuit: Breakers, Overloads, and Solutions for

    Faulty Components: Another reason for circuit breakers to trip is faulty components within the electrical system. This can include damaged wires, short circuits, or defective appliances. When these faults occur, the circuit breaker detects the problem and interrupts the current flow to prevent damage. Dealing with Constant Tripping

  10. Resettable fuse hold current and trip current

    From what I understand, the fuse will not trip when current reaches the hold current, and when the current is between the hold and trip current, what happens to the fuse is uncertain. Above the trip current, the fuse will definitely trip. So for example if I have a component that has a maximum continuous current of 5A, should I look for a ...

  11. What Does a Circuit Breaker Tripping Mean?

    Similar to an overload, when a circuit "shorts," it responds to more current than it can bear. But a short circuit is far more dangerous. A short circuit occurs when a "hot" or active wire comes into contact with either another active wire or a neutral wire. The touching wires cause a spike in current that can likewise trip your circuit breaker.

  12. What is a trip switch in physics?

    Published: July 19, 2024. Sharing is Caring. Trip switches are basically fuses; when too much current (AKA load) passes through a given circuit the switch (which are rated e.g. 13 AMP) is 'tripped' and the circuit is broken. The trip switches in the picture are all currently switched on.

  13. power supply

    When it reaches trip current, the temperature exceeds a threshhold, and the PTC becomes high resistance. The current drops due its high resistance, which removes most of the voltage from the load. As long as the supply voltage remains connected, the PTC stays hot enough to stay in that state. You should choose a PTC with a trip current

  14. Fundamental Characteristics of Circuit Breaker

    The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit breaker will trip. It also represents the maximum current that the circuit breaker can carry without tripping. That value must be greater than the maximum load current IB, but less than the maximum current permitted in the circuit Iz.

  15. The calculation of Conventional non-tripping current and Conventional

    It's exactly the same with circuit breakers and they both have the 13% overload point meaning the CBs/fuses should not trip if they were at this level all day. On the other hand, the 45% overload level should trip after 1 hour and at 155% overload (2.55 times rated current) it should trip after one minute.

  16. What is a Trip Curve? Understanding Circuit Breaker Trip Curves From

    A trip curve is simply a description of how an overcurrent based on time will trip a fuse or circuit breaker. For this video we'll focus on breakers but the same applies to fuses. You may see breakers sold based on trip curve. Looking at the curve chart, this axis is time and this one is amperage as a multiple of rated current.

  17. Power circuit breaker ratings explained

    An engineer can safely apply a circuit breaker in a power system where the available short-circuit fault current on the supply side terminals does not exceed its maximum interrupting rating. Short-time current ratings defined. The short-time current rating of a circuit breaker is the ability of the circuit breaker to withstand the effects of ...

  18. Understanding Miniature Circuit Breaker (MCB) Tripping and ...

    Miniature Circuit Breaker (MCB) Trip calculation. First, look for the amperage marking on the switch of the MCB. This is usually between 15 or 20. Also look for the voltage marking on the breaker switch, this will be between 120 or 240. Second, locating the voltage and current rating, multiply the volts and the amps.

  19. Understanding Why Your Circuit Breaker Keeps Tripping

    Check the Reasons: Inspect the circuit box again and check whether any of the above reasons tick the current situation of your circuit breaker. Switch on the Devices: You need to test the circuit by switching on all the lights and appliances you unplugged. This gives you an idea of what is causing the breaker to trip.

  20. Circuit breaker

    A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent).Its basic function is to interrupt current flow to protect equipment and to prevent fire.Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or ...

  21. Time Current Curve Basics: Determining Circuit Breaker Trip Times

    Every circuit breaker has a characteristic curve that reports the manner in which it trips. As this curve is reporting the amount of current vs time, it is a...

  22. The essence of LV circuit breakers

    1.3 Electronic Release. A coil, placed on each conductor, continuously measures the current in each of them. This information is processed by an electronic module which controls the tripping of the circuit breaker when the values of the settings are exceeded. Figure 3 - Typical tripping curve for an electronic release.

  23. Procedure for Calculating the Trip Current Rating

    The result is the trip current rating. Example 1: Determine the thermal unit selection and trip current rating for thermal units in a Class 8536 Type SCG3 Size 1 magnetic starter used to control a three-phase, 1.15 service factor motor with a full-load current of 17.0 Amperes, where the motor and controller are both located in a 40 o C (104 o F ...