What is Trip-Free and Why do I need it?

A Trip-Free circuit breaker / supplementary protector is one that will trip open even if the ON-OFF mechanism is held in the ON position.  This is an important characteristic of a circuit breaker as it protects humans and equipment from the hazards of overcurrent.  If a breaker is tripping, it is doing its job.  When its not doing its job wires can overheat and start fires, motors can burn out, people can be seriously injured.  Read further for a more in-depth explanation.

Trip-Free & Trip-Free, Cycling

According to UL1077: 

A “Trip-Free” supplementary protector is, “a protector designed so that the contacts cannot be held in the closed position by the operating means during trip command conditions.” In other words, a “Trip-Free” device has the ability to automatically open a circuit in a fault situation, even though its actuator is physically held in the “on” position. This could also be thought of as “Trip-Free, Non-Cycling” (in contrast to the “Trip-Free-Cycling” described below) by UL1077’s requirements, as the contacts should remain in the open position until the actuator is released and reset.

A “Trip-Free, Cycling” supplementary protector (aka, Cycling Trip-Free) is, “a protector designed so that the contacts cannot be held in the closed position by the operating means during trip command conditions, but will reclose when the closing command is maintained. The protector will continue to close momentarily and repeatedly as long as the close command is maintained by the operating means during trip-command conditions.” In other words, a “Trip-Free, Cycling” device, with its actuator held in the “on” position, will act as an automatic-reset protective device as long as the fault condition is present, cycling repeatedly between opened and closed circuit conditions until such time as the fault is removed or the device fails.

While the mechanisms required of “Trip-Free” devices make them generally more expensive than “Trip-Free, Cycling” types, due to various design issues associated with the end product, one type of mechanism may be preferable over the other. Despite the designer’s preference, close attention should be paid to the agency standards applicable to the end product. Dictates within specific standards may mandate the use of one type of operating mechanism over the other.

Get Fresh Blog Updates

Featured resources.

Featured-Resource

MP Short Thermal Breakers Data Sheet

Get the Data Sheet

Product Catalog

Download Catalog

Get Updates by Email

Receive updates on Mechanical Products and industry news and trends.

Mechanical-Products-BG

Mechanical Products Resources

Download the Circuit Breaker Selection Guide.  Covering ratings of 0.5 – 300 amps, the selection guide is a summary overview of the Series of circuit breakers made by MP.  For further details, the individual Series Data Sheets may be downloaded.

View Resources

Latest MP Articles

View All MP Articles

  • MP Headquarters
  • 1112 N. Garfield St
  • Lombard, IL 60148
  • 630.953.4100

Circuit Protection Devices

Trip-free/nontrip-free circuit breakers.

Circuit breakers are classified as being trip free or nontrip free. A trip-free circuit breaker is a circuit breaker that will trip (open) even if the operating mechanism (ON-OFF switch) is held in the ON position. A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the operating mechanism ON

trip free circuit breaker meaning

Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on nonemergency circuits. Examples of these are precision or current sensitive circuits, nonemergency lighting circuits, and nonessential equipment circuits. Nontrip-free circuit breakers are used for circuits that are essential for operations. Examples of these circuits are emergency lighting, required control circuits, and essential equipment circuits.

PAY AFTER YOU PASS! All Courses FREE to Take - Pay only for the Certificate Record Dismiss

Username or Email Address

Remember Me

  • Mechanical & Electrical

Basics of low-voltage circuit breakers

A circuit breaker is designed to keep an undesirably large amount of current, voltage, or power out of a given part of an electrical circuit. industrial circuit breaker categories tend to follow voltage classes, which are divided according to magnitude. the ieee divides voltage systems into four classes listed in the table titled "ieee voltage classifications..

A circuit breaker is designed to keep an undesirably large amount of current, voltage, or power out of a given part of an electrical circuit.

Industrial circuit breaker categories tend to follow voltage classes, which are divided according to magnitude. The IEEE divides voltage systems into four classes listed in the table titled “IEEE voltage classifications.”

Circuit breakers found in industrial plants accommodate all voltage levels. However, low and medium-voltage circuit breakers comprise the lion’s share of switchgear used in industrial manufacturing plants. The focus of this article is limited to low-voltage circuit breakers.

The main classifications of low-voltage circuit breakers are “toggle” mechanism and two-step stored energy mechanism circuit breakers. The molded-case circuit breaker (MCCB) (Fig. 1) has a toggle mechanism with a distinct tripped position, which is typically midway between on and off.

The low-voltage power circuit breaker (LVPCB) (Fig. 2) has a two-step stored energy mechanism. This type of mechanism uses an energy storage device, such as a spring, that is “charged” and then released, or “discharged,” to close the circuit breaker. The LVPCB is older technology. Therefore the trend is away from LVPCB and toward insulated case circuit breakers (ICCB) because of reduced maintenance. No dust or contaminants can get into the sealed compartments of the ICCB and components are designed to ensure longer life.

Circuit breaker construction

As shown in Fig. 3, most circuit breakers have five main components:

Frame or molded case

Operating mechanism

Arc extinguishers and contacts

Terminal connectors

Trip bar or element.

The frame provides an insulated housing and is used to mount the circuit breaker components. The frame determines the physical size of the circuit breaker and the maximum allowable voltage and current. The operating mechanism provides a means of opening and closing the breaker contacts. In addition to indicating whether the breaker is open or closed, the operating mechanism handle indicates when the breaker has opened automatically (tripped) by moving to a position between on and off. To reset the circuit breaker, first move the handle to the “off” position, and then to the “on” position.

The arc extinguisher confines, divides, and extinguishes the arc drawn between contacts each time the circuit breaker interrupts current. The arc extinguisher is actually a series of contacts that open gradually, dividing the arc and making it easier to confine and extinguish (Fig. 4). Arc extinguishers are generally used in circuit breakers that control a large amount of power, such as those found in power distribution panels. Small power circuit breakers, such as those found in lighting panels, may not have arc extinguishers.

Terminal connectors are electrically connected to the contacts of the circuit breaker and provide the means of connecting the circuit breaker to the circuit. The trip element is the part of the circuit breaker that senses the overload condition and causes the circuit breaker to trip or break the circuit. Some circuit breakers use solid-state trip units, which use current transformers and solid-state circuitry.

Trip elements

The thermal trip element circuit breaker, like a delay fuse, protects a circuit from a small overload that continues for a long time (Fig. 5). The larger the overload, the faster the circuit breaker trips. The thermal element also protects the circuit from temperature increases. A magnetic circuit breaker trips instantly when the preset current is present. In some applications, both types of protection are desired. Rather than use two separate circuit breakers, a single trip element combining thermal and magnetic trip elements is used.

A magnetic trip element circuit breaker uses an electromagnet in series with the circuit load. With normal current, the electromagnet does not have enough attraction to the trip bar to move it; the contacts remain closed. The strength of the magnetic field of the electromagnet increases as current through the coil increases. As soon as the current in the circuit becomes large enough, the trip bar is pulled toward the magnetic element (electromagnet), the contacts are opened, and the current stops.

The amount of current needed to trip the circuit breaker depends on the size of the gap between the trip bar and the magnetic element. On some circuit breakers, this gap, and therefore the trip current, is adjustable.

In the thermal-magnetic trip element circuit breaker, a magnetic element is connected in series with the circuit load, and the load current heats a bimetallic element. Thermal-magnetic trip element operation is detailed in Fig. 6a and 6b.

Trip-free and nontrip-free circuit breakers

Circuit breakers are classified as being trip free or nontrip free. A trip-free circuit breaker is a circuit breaker that trips even if the operating mechanism is held in the “on” position. A nontrip-free circuit breaker can be reset and/or held “on” even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the operating mechanism “on.”

Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on nonemergency circuits. Examples of these are precision or current sensitive circuits, nonemergency lighting circuits, and nonessential equipment circuits. Nontrip-free circuit breakers are used for circuits that are essential for operations. Examples of these circuits are emergency lighting, required control circuits, and essential equipment circuits.

Circuit breaker maintenance

Circuit breakers that can be accessed for maintenance require careful inspection and periodic cleaning. Before you attempt to work on circuit breakers, check the applicable technical manual carefully. Remove power to the circuit breaker before you work on it. Tag the switch that removes the power from the circuit breaker to ensure that power is not applied while you are working.

Manually operate the circuit breaker several times to ensure the operating mechanism works smoothly. Inspect the contacts for pitting caused by arcing or corrosion. If pitting is present, smooth the contacts with a fine file or number 00 sandpaper.

Be certain the contacts make proper contact when the operating mechanism is in the “on” position.

Check the connections at the terminals to ensure the terminals and wiring are tight and free from corrosion. Check all mounting hardware for tightness and wear. Check all components for wear. Clean the circuit breaker completely.

When you have finished working on the circuit breaker, restore power and remove the tag from the switch that applies power to the circuit.

PLANT ENGINEERING magazine extends its appreciation to Eaton | Cutler-Hammer, E-T-A Circuit Breakers, Rockwell Automation, Schneider Electric, and Siemens Energy & Automation, Inc., for the use of their materials in the preparation of this article.

IEEE voltage classifications

Low-voltage systems.

&1000 Vac

Medium-voltage systems

>1000 Vac to

100,000 Vac*

High-voltage systems

>100,000 Vac to

230,000 Vac

Extra-high voltage systems

>230,000 Vac to 800,000 Vac

*Most medium-voltage systems are rated at 38000 Vac or less.

Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our CFE Media editorial team and getting the recognition you and your company deserve. Click here to start this process.

Related Resources

trip free circuit breaker meaning

Privacy Overview

trip free circuit breaker meaning

TRIP-FREE/NONTRIP-FREE CIRCUIT BREAKERS

Circuit breakers are classified as being trip free or nontrip free.

A trip-free circuit breaker is a circuit breaker that will trip (open) even if the operating mechanism (ON-OFF switch) is held in the ON position. A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the operating mechanism ON.

Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on nonemergency circuits. Examples of these are precision or current sensitive circuits, nonemergency lighting circuits, and nonessential equipment circuits.

Nontrip-free circuit breakers are used for circuits that are essential for operations. Examples of these circuits are emergency lighting, required control circuits, and essential equipment circuits.

TIME DELAY RATINGS

Circuit breakers, like fuses, are rated by the amount of time delay. In circuit breakers the ratings are instantaneous, short time delay, and longtime delay. The delay times of circuit breakers can be used to provide for SELECTIVE TRIPPING.

Selective tripping is used to cause the circuit breaker closest to the faulty circuit to trip. This will remove power from the faulty circuit without affecting other, nonfaulty circuits. Figure 2-22 should help you understand selective tripping.

Figure 2-22. - Use of circuit breakers in a power distribution system.

32NE0283.GIF (19918 bytes)

Figure 2-22 shows a power distribution system using circuit breakers for protection. Circuit breaker 1 (CB1) has the entire current for all seven loads through it. CB2 feeds loads 1, 2, 3, and 4 (through CB4, CB5, CB6, and CB7), and CB3 feeds loads 5, 6, and 7 (through CB8, CB9, and CB10). If all the circuit breakers were rated with the same time delay, an overload on load 5 could cause CB1, CB3, and CB8 to trip. This would remove power from all seven loads, even though load 5 was the only circuit with an overload.

Selective tripping would have CB1 rated as long time delay, CB2 and CB3 rated as short time delay, and CB4 through CB10 rated as instantaneous.

With this arrangement, if load 5 had an overload, only CB8 would trip. CB8 would remove the power from load 5 before CB1 or CB3 could react to the overload.

In this way, only load 5 would be affected and the other circuits would continue to operate.

PHYSICAL TYPES OF CIRCUIT BREAKER S

All the circuit breakers presented so far in this chapter have been physically large, designed to control large amounts of power, and used a type of toggle operating mechanism. Not all circuit breakers are of this type. The circuit breaker in figure 2-23 is physically large and controls large amounts of power; but the operating mechanism is not a toggle. Except for the difference in the operating mechanism, this circuit breaker is identical to the circuit breakers already presented.

Figure 2-23. - Circuit breaker with an operating handle.

32NE0284.GIF (31201 bytes)

Circuit breakers used for low power protection, such as 28-volt dc, 30 amperes, can be physically small. With low power use, arc extinguishers are not required, and so are not used in the construction of these circuit breakers . Figure 2-24 shows a low power circuit breaker of the push-button or push-pull type. This circuit breaker has a thermal trip element (the bimetallic disk) and is nontrip-free. The push button is the operating mechanism of this circuit breaker .

Figure 2-24. - Push-button circuit breaker.

32NE0285.GIF (3370 bytes)

You will find other physical types of circuit breakers as you work with electrical circuits. They are found in power distribution systems, lighting panels, and even on individual pieces of equipment. Regardless of the physical size and the amount of power through the circuit breaker, the basic operating principles of circuit breakers apply.

trip free circuit breaker meaning

Manual Trip - ON/OFF Switches

Many models are available with a manual trip feature, either standard or as an option.

Others are specifically designed as combined switch/circuit breakers

with rocker, push button, or toggle actuation, styled for front panel mounting. Rocker types are available with illumination as an option.

According to IEC 934/EN 60934:

  • R = manual reset only
  • M = with manual release but not intended for frequent use as a switch
  • S = combined switch/CBE function
  • J = automatic reset

Trip Free Mechanism

E-T-A circuit breakers cannot be held closed against an overload. This is achieved through the use of positively trip free designs in accordance with IEC 934/EN 60934 (with the exception of models 1410, 1610, 1658 and 808 which are designed for specialised applications).

Snap-Action Mechanism

The snap-action mechanism featured in many E-T-A models ensures that the contact closing speed is independent of the speed of operation of the actuator (push button, rocker, toggle etc.). The moving contact is retained until the actuator causes a defined force to act in the closing direction of the contacts. Once this force is exceeded, the mechanical retention is overcome allowing the contacts to snap closed (tease free mechanism.) The closing speed is a function of this force alone.

Snap-action mechanisms eliminate contact welding upon switching on to sustained short-circuits and minimise the risk of contact wear over the circuit breakers' life.

  • International

trip free circuit breaker meaning

Privacy Statement Press Release Contact

  • Transformers

What are Trip Free and non-Trip Free Circuit Breakers

trip free circuit breaker meaning

  • Motors and Drives
  • Energy Efficiency

Circuit breakers with a trip-free design

Phoenix contact's ul 489 listed circuit breakers has a trip-free design that increases safety against closing during an overcurrent event, while the snap-action mechanism eliminates contact welding and reduces contact wear..

Phoenix Contact’s the TMC 8 series UL 489 Listed circuit breakers has a trip-free design that increases safety against closing during an overcurrent event, while the snap-action mechanism eliminates contact welding and reduces contact wear. These circuit breakers safely open circuits during overload and short-circuit events, which prevents the wiring from causing fires. The TMC 8 series breakers are available in 1-, 2-, and 3-pole options, with B-, C-, and D-trip curves, to accommodate a variety of applications. The breakers also include visual trip status indication and several accessories, including auxiliary contact, alarm contact, shunt trip, and cuttable busbars.

Phoenix Contact

www.phoenixcontact.com

– Edited by CFE Media. See more  Control Engineering   energy and power products .

Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our CFE Media editorial team and getting the recognition you and your company deserve. Click here to start this process.

  • Electronic circuit breakers for control systems
  • Generator paralleling switchgear
  • Circuit breaker for underground mining and metals operations

Eau Claire, US

Columbia, US

Windsor, CA

Redmond, US

Privacy Overview

Filipino Engineer

What is a trip free circuit breaker?

trip free circuit breaker meaning

A trip-free circuit breaker is a type of circuit breaker that cannot be forcibly held closed (or in the "on" position) during an overcurrent or fault condition. In simpler terms, even if someone tries to manually keep the circuit breaker "on", it will still "trip" or automatically turn off if a fault is detected. A trip-free circuit breaker is commonly used in electrical distribution systems to prevent damage to electrical equipment and circuits in the event of overcurrent or short-circuit conditions. The term "trip-free" refers to a specific feature of the circuit breaker, which distinguishes it from other types of circuit breakers.

In a conventional circuit breaker, there are typically two modes of operation:

A trip-free circuit breaker, on the other hand, has a feature that prevents the immediate resetting of the circuit breaker while there is still an ongoing fault condition or overcurrent situation. In other words, even if someone tries to manually reset the circuit breaker, it will not reset until the fault is cleared or the overcurrent condition subsides.

This feature is designed to enhance safety by ensuring that the circuit breaker remains in the "OFF" position as long as there is a potentially hazardous electrical fault. It prevents accidental or deliberate attempts to reset the circuit breaker in situations where doing so could lead to electrical hazards or equipment damage.

Importance of Trip-Free Circuit Breakers

  • To save this word, you'll need to log in. Log In

Definition of trip-free

Love words.

You must — there are over 200,000 words in our free online dictionary, but you are looking for one that’s only in the Merriam-Webster Unabridged Dictionary.

Start your free trial today and get unlimited access to America's largest dictionary, with:

  • More than 250,000 words that aren't in our free dictionary
  • Expanded definitions, etymologies, and usage notes
  • Advanced search features

Dictionary Entries Near trip-free

tripetalous

Cite this Entry

“Trip-free.” Merriam-Webster.com Dictionary , Merriam-Webster, https://www.merriam-webster.com/dictionary/trip-free. Accessed 11 Apr. 2024.

Subscribe to America's largest dictionary and get thousands more definitions and advanced search—ad free!

Play Quordle: Guess all four words in a limited number of tries.  Each of your guesses must be a real 5-letter word.

Can you solve 4 words at once?

Word of the day.

See Definitions and Examples »

Get Word of the Day daily email!

Popular in Grammar & Usage

Your vs. you're: how to use them correctly, every letter is silent, sometimes: a-z list of examples, more commonly mispronounced words, how to use em dashes (—), en dashes (–) , and hyphens (-), absent letters that are heard anyway, popular in wordplay, the words of the week - apr. 5, 12 bird names that sound like compliments, 10 scrabble words without any vowels, 12 more bird names that sound like insults (and sometimes are), 8 uncommon words related to love, games & quizzes.

Play Blossom: Solve today's spelling word game by finding as many words as you can using just 7 letters. Longer words score more points.

ApplianceTeacher logo

What Causes a Circuit Breaker to Trip?

Trevor

Circuit breakers are an essential component of any home electrical system. They are designed to protect our homes and appliances from electrical overloads and short circuits. But what causes a circuit breaker to trip, and how can we prevent it from happening? In this comprehensive guide, we’ll delve into the common reasons why circuit breakers trip and provide some practical tips to avoid this problem.

A circuit breaker may trip due to three primary reasons: overloads, short circuits, and ground fault surges. Overloads occur when a circuit draws more power than it can handle, usually due to too many appliances operating on the same circuit. Short circuits and ground fault surges happen when a hot wire comes into contact with a neutral wire or a ground wire, causing a large amount of current to flow and overheat the circuit. Less common causes can include faulty wiring, a damaged breaker, or power surges from storms and lightning strikes.

Understanding Circuit Breakers

Before we dive into the reasons, it’s important to understand what a circuit breaker is and how it works. A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent, overload, or short circuit. Its primary function is to interrupt the current flow when it detects a fault in the electrical system, thereby protecting equipment and preventing the risk of fire.

Circuit breakers can be reset either manually or automatically to resume normal operation, unlike fuses which must be replaced after operating once. They come in various sizes, from small devices that protect low-current circuits or individual household appliances to large switchgear designed to protect high voltage circuits feeding an entire city.

Common Reasons for a Circuit Breaker to Trip

There are three primary reasons why a circuit breaker might trip:

  • Overloads : This is the most common reason for a circuit breaker to trip. Overloads occur when a circuit is drawing more power than its rated capacity. This can happen when too many appliances or devices are operating on the same circuit at the same time.
  • Short Circuits : A short circuit is a more serious issue. It occurs when a “hot” wire comes into contact with a neutral wire in one of your outlets. This can cause a large amount of current to flow, creating more heat than the circuit can handle, which in turn causes the circuit breaker to trip.
  • Ground Fault Surges : Similar to a short circuit, a ground fault surge happens when a hot wire comes into contact with a ground wire or the metal box that houses the wiring. This causes a sudden rush of electricity that can heat up the circuit, causing the breaker to trip.

Other less common reasons for a circuit breaker to trip include faulty wiring, a damaged breaker, or power surges from storms and lightning strikes.

Preventing Circuit Breakers from Tripping

Here are some practical tips to prevent circuit breakers from tripping frequently:

  • Distribute Electrical Devices : Avoid plugging too many devices into one circuit. Instead, distribute them across multiple circuits to balance the load.
  • Inspect and Replace Old Wiring : Old and faulty wiring can cause short circuits or ground faults. Regular inspection and replacement of old wiring can prevent these issues.
  • Use Surge Protectors : Surge protectors can protect your devices and prevent circuit breakers from tripping during power surges.
  • Replace Old or Damaged Circuit Breakers : If your circuit breaker is old or damaged, it may trip more frequently. Consider replacing it with a new one.

In conclusion, circuit breakers play a vital role in maintaining the safety of our homes. Understanding why they trip and how to prevent it can help us maintain a safe and efficient electrical system. If your circuit breaker continues to trip frequently, it’s best to consult a professional electrician to diagnose and fix the problem. Remember, dealing with electricity can be dangerous, and it’s always better to be safe than sorry.

Frequently Asked Questions

What is the difference between a circuit breaker and a fuse.

Both circuit breakers and fuses serve the same purpose – to protect an electrical circuit from damage caused by an overcurrent, overload, or short circuit. The main difference is how they handle the fault condition. A fuse will melt when overloaded, interrupting the circuit but requiring replacement. On the other hand, a circuit breaker will simply trip (switch off) and can be reset either manually or automatically to resume normal operation.

How can I tell if my circuit breaker is faulty?

Common signs of a faulty circuit breaker include the breaker constantly tripping, the breaker not staying reset, a burning smell or visible burn marks around the breaker, or physical damage to the breaker itself. If you suspect your circuit breaker is faulty, it’s best to consult a professional electrician.

How often should circuit breakers be replaced?

There’s no hard and fast rule for when to replace a circuit breaker. They can last for many years, even decades, if they’re not exposed to excessive moisture or heat and are not constantly being tripped. However, if you’re experiencing frequent tripping or other issues, it’s a good idea to have them inspected by a professional electrician, who can recommend replacement if necessary.

Can I reset a tripped circuit breaker myself?

Yes, you can usually reset a tripped circuit breaker yourself. First, identify the tripped breaker in your electrical panel. It will typically be in the “off” position or in a middle position between “on” and “off.” Simply switch the breaker to the “off” position and then back to the “on” position. However, if the breaker continues to trip, it’s best to consult a professional electrician as it could be a sign of a more serious problem.

Related Posts

Washing Machine

What Does “CL” Mean on an LG Washer?

Hair Dryer

How To Wrap Hot Water Heater Pipes

Dryer Vent Filled With Lint

How To Prevent Lint Build-Up In Dryer Vent

Circuit Breaker

How To Reset Circuit Breaker with Test Button

Air Conditioner

How To Stop Draft from Air Conditioner

Dryer

What Dryer Belt Do I Need?

About the author, trevor ritter, leave a comment cancel reply.

Your email address will not be published. Required fields are marked *

Save my name, email, and website in this browser for the next time I comment.

Trevor is an appliance repair technician with years of experience fixing all sorts of appliances. He enjoys sharing his knowledge so that others can avoid common mistakes when repairing appliances.

Dryer

How To Clean a Kenmore Dryer

Dishwasher

What Does "Max Height" on a Dishwasher Mean?

Toaster Oven

What Is the Purpose of a Toaster Oven?

Air Conditioner

How To Set Auto Mode in LG AC

Microwave

Where Is the Charcoal Filter on a GE Microwave?

Dishwasher

How To Disable the Child Lock on a Samsung Dishwasher

800-999-7378

Airline logo

  • All blog posts

airline_logo_1920x640

In this industrial blog, learn how to make your technology systems work for you . Become faster, smarter, competitive, and cost-effective in today's rapidly changing marketplace by learning from our experts' collective experience. Bookmark our page (or better yet, subscribe ) because we post new articles every Thursday!

trip free circuit breaker meaning

Circuit Breaker Trip Curves: What Electrical Control Panel Builders Need to Know

Bill Lallone

Circuit breakers are essential devices in electrical systems, protecting against harmful overcurrent conditions. An improperly-selected circuit breaker causes, at best, nuisance tripping . At worst, it causes damage to electrical equipment, electrical fires, and serious or fatal injuries. A critical factor in selecting circuit breakers is understanding the trip curve , which visually represents how quickly it will trip or open in response to different levels of overcurrent. But trip curves are notoriously confusing, so keep reading to learn the basics of trip curves to select the most appropriate and cost-effective breaker for your application.

Skip to a Section 

What are Trip Curves? | Trip Curve Types |  UL 1077 or UL 489? | How to Choose  

What are Trip Curves?

Circuit breaker trip curves are graphical representations of the response time of a circuit breaker to overcurrent conditions. They show the relationship between the level of current flowing through a circuit and the time it takes for the circuit breaker to trip or interrupt the current. An example of a trip curve is shown below.

image

The trip curve helps electrical control panel builders understand how a circuit breaker will behave under different fault conditions, such as overloads or short circuits. By matching the trip curve with the characteristics of the application, electrical control panel builders can select the correct size and type of circuit breaker, with minimal or no nuisance tripping, at the lowest possible cost.

Trip Curve Types

trip curve example

Thermal Region of Trip Curve

The thermal section of the trip curve responds to overloads (sustained or long-lasting overcurrent conditions) and is represented by the top/red area of the left graph. Therefore, a circuit breaker with a thermal trip curve is better suited for high-inrush current applications. The thermal trip curve is typically curved , reflecting the fact that the response time of the circuit breaker increases as the level of overcurrent increases. The thermal trip unit responds relatively slowly yet consistently.

Magnetic Region of Trip Curve

The magnetic current section of the trip curve responds to short circuits and is represented by the bottom/gray area of the graph above. It relies on a magnetic coil or solenoid opening when the overcurrent’s design limit is reached. The magnetic trip curve is typically a straight line , reflecting the fact that the response time of the circuit breaker is nearly instantaneous for high levels of current.

Characteristics of the magnetic/short-circuit trip unit

The characteristics of the magnetic/short-circuit trip unit and applications of each curve, from most to least sensitive, are:

Z : Trips at 2 to 3 times rated current. This is suitable for highly sensitive applications, e.g., semiconductor devices.

B : Trips at 3 to 5 times rated current.

C : Trips at 5 to 10 times rated current, making it suitable for medium inrush currents.

K : Trips at 10 to 14 times rated current. This suits loads with high inrush currents, mostly for motors and transformers.

D : Trips at 10 to 20 times rated current, making it suitable for high starting currents.

Instantaneous Region of Trip Curve

Sometimes, a trip curve will include an instantaneous region. The instantaneous trip curve is usually represented by a vertical line , indicating the maximum current level that the circuit breaker can interrupt without any delay .

What Do UL 1077 and UL 489 Mean? 

In addition to trip curves, understanding UL certifications is another key component to selecting circuit breakers. UL-certified circuit breakers are a type of circuit breaker that is certified by Underwriters Laboratories ( UL ) and meets their requirements for construction, performance, and testing.

UL 489 and UL 1077 circuit breakers have different trip curves for specific applications. It is important to note that both standards require passing calibration, overload, endurance, and short-circuit tests, but UL 489 testing is more rigorous than UL 1077 testing . Choosing the appropriate UL-certified circuit breaker with the correct trip curve is vital to ensure proper protection and avoid damage and downtime.

What is UL 489?

UL 489 is a standard for molded-case circuit breakers , which are commonly used in commercial and industrial applications.  One of the key features of UL 489 circuit breakers is their ability to interrupt short-circuit currents. This is important because short circuits can generate extremely high currents that can damage equipment and pose a safety hazard. UL 489 circuit breakers are also designed to be reliable and durable, with a long lifespan and minimal maintenance requirements.

What is UL 1077?

UL 1077 is a standard for supplementary protectors , which are commonly used in low-voltage DC or AC circuits. UL 1077 circuit breakers are designed to be compact and cost-effective, making them well-suited for applications where space and budget constraints are a concern. But i t is essential to note UL 1077 devices are not considered circuit breakers by UL and are defined as supplementary protectors. 

How to Choose a Circuit Breaker with the Right Trip Curve

3409420

Here are four general guidelines to help select the appropriate breaker:

  • 1. Identify the load type:
  • The load connected to the circuit breaker is an essential factor to consider when selecting the trip curve. For example, loads like motors and transformers have high inrush currents, and a faster-acting trip curve can cause nuisance tripping. Therefore, a circuit breaker with a slower trip curve or a higher magnetic trip point is more suitable for these types of loads.
  • 2. Evaluate the expected fault conditions:
  • Fault conditions like overloads, short circuits, and ground faults have different characteristics and require other response times from the circuit breaker. Therefore, a circuit breaker with a trip curve that matches the expected fault conditions will provide optimal protection.
  • 3. Consider system coordination:
  • 4. Consult with the manufacturer or supplier:
  • The manufacturer or supplier of the circuit breaker can provide valuable guidance on selecting the appropriate trip curve for a given application. They can also provide information on specific trip curves compatible with the circuit breaker and recommend a suitable trip curve based on the application's requirements.
  • In general, understanding trip curves and UL certifications is crucial for selecting the proper protective devices for your electrical applications. If in doubt, a consultation with the manufacturer or value-add distributor, like Airline , can help make an informed decision. 
  • Have a question? Let us know!

Contact Us! 

Resources 

  • Shop Circuit Breakers 
  • Shop Minature Breakers 
  • IEC General Rules
  • A  Guide on UL Standards 
  • Contact Us! 

Topics: Electrical , Explainers

Leave Comment

Subscribe to our blog, most recent, post by topic.

  • Explainers (76)
  • Product Spotlights (51)
  • Automation (32)
  • Electrical (32)
  • Hydraulics (22)
  • Pneumatics (16)
  • About Airline (15)
  • Robotics (15)
  • Maintenance (14)
  • Phoenix Contact (13)
  • Tutorials (13)
  • Framing (11)
  • Machine Safety (11)
  • Application/Success Stories (10)
  • Bosch Rexroth (hydraulics) (10)
  • Bosch Rexroth (framing) (6)
  • Lean Manufacturing (5)
  • Liquid & Gas Prssure (5)
  • Lubrication (5)
  • Lincoln SKF (4)
  • Bosch Rexroth (linear) (3)
  • Fluid Cleanliness (3)
  • Predictive Maintenance (3)
  • Clippard (2)
  • Grace Technologies (2)
  • Bosch Rexroth (automation and controls) (1)
  • Case study (1)
  • Compliance (1)
  • In-Person Events (1)
  • Lab Safety (1)
  • QC Conveyors (1)
  • Trainings (1)

airline girl

Buell Electric Dunedin FL

1335 Martin Luther King Jr Ave

Dunedin, fl 34698, (727) 648-6101.

Buell Electric

1335 Martin Luther King Jr Ave, Dunedin, FL 34698

CALL US:   (727) 648-6101

Buell Electric

What Does a Circuit Breaker Tripping Mean?

 when there's a circuit breaker tripping, it can indicate that the circuit breaker detects an electrical issue, and it shouldn't be ignored..

circuit breaker tripping

The pandemic-induced surge in home electricity use is real. Consider that, according to the National Bureau of Economic Research, American spending on  home power consump tion  skyrocketed by $6 billion! 

With more usage comes more problems, and circuit breaker issues are among the most common. When there's a circuit breaker tripping, it can indicate that the circuit breaker detects an electrical issue, and it shouldn't be ignored.

 Circuit Breaker Tripping 101

Most circuit breaker issues center around circuit overload. Circuit breakers are a vital part of your home's electrical system since they are designed to prevent costly and damaging surges in electrical current. 

The breaker, working in tandem with a fuse, serves as an electrical unit's internal sensing mechanism. At the slightest sense of excess current, the circuit breaker will "trip," triggering a cease in all electrical activity within the circuit.

Not only can such a smart mechanism help with preventing damage to wires and other electrical components, but circuit breakers can also save lives by preventing electrical fires. According to the National Fire Protection Association,  electrical failures  were the second leading cause of home fires between 2012-2016.

So why do circuit breakers trip? Here are the three most common reasons for circuit breaker tripping and how you can go about fixing a circuit breaker.

 1) Circuit Overload

By far, the m ost common reason a circuit trips is because it's overloaded. Even running a circuit at its electrical capacity can cause home appliances to burn out or a circuit to trip. Ideally, you want to run a circuit below its capacity to keep it from tripping and to prevent any damage from occurring. 

The most familiar example of circuit overload is an over-stuffed power outlet. When you have a dozen gadgets all demanding electrical current to work, eventually that single outlet's capacity will experience overload, and the circuit will trip.

Knowing what each electrical outlet in your house can handle is key to preventing circuit overload. Even a single high-current appliance like a washing machine cannot plug into just any outlet.  Understanding your power outlets  is critical for a safer home.

Before you head to your circuit breaker box or call your electrician, notice what was plugged in at the outlet where the tripped circuit occurred. You may have overloaded it.

 2) Short Circuit

Similar to an overload, when a circuit "shorts," it responds to more current than it can bear. But a short circuit is far more dangerous. 

A short circuit occurs when a "hot" or active wire comes into contact with either another active wire or a neutral wire. The touching wires cause a spike in current that can likewise trip your circuit breaker. Most often, the causes for short circuits are mechanical issues like: 

  • Loose Connections
  • Improper Wiring
  • Damaged Wires

Faulty components, like switches, plugs, cords, appliances, or lighting fixtures, are often culprits of short circuits. Short circuits can occur if you screw or nail into drywall and penetrate an electrical wire.

Remember that short circuits may involve faulty circuit wiring, but the device you're plugging in can cause the problem as well. Keep this in mind, especially if you're using older devices or gadgets that have been out of commission for years, as these can be more prone to short circuits, independent of what's going on in the outlet.

Due to their volatile nature, short circuits are some of the biggest causes of electrical fires, so be extra attentive and don't hesitate to call a professional. As a general rule, most people should never  DIY electrical issues  in their homes.

 3) Ground Fault Surge

 Ground fault surges are similar to short circuits because they involve a sudden spike in current, creating an overload. Ground faults occur when an active wire comes into contact with the ground wire. The contact can come directly or indirectly via the metal housing that connects to the ground wire. 

Copper grounding wires are especially prone to ground fault surges. Copper is the most  conductive material  in everyday use when it comes to home electrical systems. When a hot wire touches the ground wire's copper coating, it results in superconductivity that overwhelms the circuit. A similar result can come from an active wire touching a ground's metal outlet box. 

 Understanding and Fixing Circuit Breaker Issues

So how should you go about troubleshooting a circuit breaker issue? Even though you should leave anything remotely technical to a professional, there are a few things you can do to investigate circuit breaker trip meaning.

First thing's first. Make sure you and your family are safe. Check for signs of excess heat or burning—smell for what could be smoke from an electrical fire. If you sense any signs of a fire, evacuate and call 911.

Check for any discoloration around an outlet. Also, make a note of any sparks or popping noises coming from the outlet. Any of these could be a sign of a ground fault surge or a short, in which case simply flipping the circuit breaker switch won't help. And remember, the older the outlet, the more likely it is to experience problems.

Look for any signs of damage to your devices. Remember that the problem could be coming, not from your home's outlet, but from what you plugged in.

If there are no signs of a blown circuit, try going to your circuit breaker service panel. You may be familiar with this metal box, often located in a garage or utility room. Flip the switch of the house area that tripped, and see if that "resets" the circuit. 

 Fixing a Circuit Breaker

If a simple flipping of the switch doesn't work, it's time to call a professional electrician. The seasoned team at Buell Electric can assess the problem and fix a circuit breaker, which may involve repairs or upgrades. 

Circuit breaker tripping may be as innocent as overloading an outlet, but it can point to more serious problems as well. The best way to know for sure is to  contact us  today.

Newer Post >

Buell Electric's Blog

home electrician tampa

Shedding Light on Your Home: Finding the Right Electrician in Tampa

changing technology

How Electricians Keep Up with Changing Technology in the Industry

electrical maintenance services

The Importance of Regular Electrical Maintenance For Your Business

marine electrical standards

Marine Electrical Standards and Regulations You Need to Know

smart home system

The Benefits of Installing a Smart Home System

electrical wiring

Understanding the Different Types of Electrical Wiring in Your Home

electrical emergency

How to Prepare Your Home for an Electrical Emergency

ceiling fan installation

5 Reasons Your Ceiling Fan Installation Should be Left to the Pros

residential electrical services

5 Tips for Hiring Residential Electrical Services

outdoor lighting mistakes

8 Common Outdoor Lighting Mistakes and How to Avoid Them

Home Advisor Screened and Approved

[email protected]

Mon-fri 9:00 am - 5:00 pm sat-sun 10:00 am - 5:00 pm privacy page, connect with us:.

Buell Electric State Certified Electrical Contractor

Mon-Fri 9:00 AM - 5:00 PM Sat-Sun 10:00 AM - 5:00 PM

All Rights Reserved | Buell Electric, Inc.

trip free circuit breaker meaning

IMAGES

  1. Why is the Breaker Tripping?

    trip free circuit breaker meaning

  2. Trip circuit of Circuit Breaker Explained with Animation_Switchgear & protection

    trip free circuit breaker meaning

  3. Common Trip and Single Pole Circuit Breakers

    trip free circuit breaker meaning

  4. Tripping Curves of Circuit Breaker. B, C, D, K & Z Trip Curve

    trip free circuit breaker meaning

  5. Shunt Trip Breaker Wiring Diagram, Connection, Circuit

    trip free circuit breaker meaning

  6. What are Inverse Time and Instantaneous Trip Circuit Breakers?

    trip free circuit breaker meaning

VIDEO

  1. PANEL AND MCB CIRCUIT BREAKER SET UP FOR 3 STOREY RESIDENTIAL HOUSE CONSTRUCTED BY REYCA WORKS

  2. How To Make Circuit Breaker Trip Indicator

  3. How to identify a trip Circuit. breaker

  4. Tripping Time of Circuit Breaker

  5. Circuit Breaker Working Principle at Slow Motion

  6. Circuit BREAKER operating open

COMMENTS

  1. What is Trip-Free and Why do I need it?

    A Trip-Free circuit breaker / supplementary protector is one that will trip open even if the ON-OFF mechanism is held in the ON position. This is an important characteristic of a circuit breaker as it protects humans and equipment from the hazards of overcurrent. If a breaker is tripping, it is doing its job.

  2. PDF The importance of trip free operation and its characteristics

    Definitions. In the most general definition of "Trip-Free," the contacts of the circuit breaker must return to the open position and remain there when an opening operation follows a closing operation, regardless of whether the closing signal, force, or action is maintained. A common variant is called "Electrically Trip-Free.".

  3. The Importance of Trip-Free Operation and Its Characteristics

    This characteristic is often confused with the definition of trip-free.However, if any opening release operation isinitiated simultaneously with any closing release operation signal, contact movement up to and including a momentary touching of the main circuit breaker contacts is acceptable before the circuit breaker completes the opening ...

  4. Trip-Free/Nontrip-Free Circuit Breakers

    A trip-free circuit breaker is a circuit breaker that will trip (open) even if the operating mechanism (ON-OFF switch) is held in the ON position. A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the ...

  5. How To Find What Is Tripping Your Circuit Breaker and Fix It

    If you suspect a short circuit, unplug your appliances and check the wires for melted coverings. You might also notice a burning smell coming from the outlet. Call in a professional electrician to find the source of the problem. 3. Circuit Overload. Circuit overloads are the most common reason that a breaker trips.

  6. Trip free operating mechanism definition acc to IEEE C37.04

    Trip free operating mechanism definition acc to IEEE C37.04. Medium voltage circuit breakers tripfree definition in the standard are: If a closing operation is in progress, and a tripping signal (either mechanical or electrical) is received, the circuit breaker shall react as follows: simultaneously, the circuitbreaker contacts are permitted to ...

  7. Basics of low-voltage circuit breakers

    A nontrip-free circuit breaker can be reset and/or held "on" even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the operating mechanism "on." Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on nonemergency circuits.

  8. What Is Trip-Free Mechanism and Why Do I Need It?

    Conclusion. Modern circuit-breakers are designed with a free trip mechanism that ensures unconditional disconnection of both overcurrent and short-circuit current, even if the push-button is locked in the "on" position. This mechanism allows the circuit breaker to trip automatically in the event of an electrical fault, providing protection ...

  9. Trip-Free/Nontrip-Free Circuit Breakers

    A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the operating mechanism ON. Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on nonemergency circuits.

  10. Circuit Breakers

    Trip Free Mechanism E-T-A circuit breakers cannot be held closed against an overload. This is achieved through the use of positively trip free designs in accordance with IEC 934/EN 60934 (with the exception of models 1410, 1610, 1658 and 808 which are designed for specialised applications).

  11. TRIP-FREE/NONTRIP-FREE CIRCUIT BREAKERS

    A trip-free circuit breaker is a circuit breaker that will trip (open) even if the operating mechanism (ON-OFF switch) is held in the ON position. A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip-free circuit breaker can be bypassed by holding the ...

  12. What are Trip Free and non-Trip Free Circuit Breakers

    Non-Trip Free circuit breakers are used in circuits which are critical for plant operation and for safety. In these systems, it may be economical to lose a motor or a heater than to interrupt the manufacturing process. In these circuit breakers, the trip function can be bypassed by forcing the circuit breaker to the on position.

  13. Circuit breakers with a trip-free design

    By Phoenix Contact July 3, 2016. Phoenix Contact's the TMC 8 series UL 489 Listed circuit breakers has a trip-free design that increases safety against closing during an overcurrent event, while the snap-action mechanism eliminates contact welding and reduces contact wear. These circuit breakers safely open circuits during overload and short ...

  14. What is the difference between a "handle tie" and "common trip" in

    That wouldn't work because the handles "trip free" - that is, if the breaker needs to trip and a padlock or naughty human is impeding the handle from moving, the breaker just trips anyway. So if the other half of the breaker impeded the handle from moving, the side that tripped would just trip anyway, and common trip would not occur.

  15. What is a trip free circuit breaker?

    Definition. A trip-free circuit breaker is a type of circuit breaker that cannot be forcibly held closed (or in the "on" position) during an overcurrent or fault condition. In simpler terms, even if someone tries to manually keep the circuit breaker "on", it will still "trip" or automatically turn off if a fault is detected. ...

  16. How To Fix a Circuit Breaker That Keeps Tripping

    Find out the cost to replace an electrical panel. On every breaker, there will be an "On" and "Off" position. On a tripped breaker, the handle will be in the middle, neither On nor Off. To reset, flip the handle to Off first, then to On. Stand to the side of the panel and turn your face away when flipping breakers.

  17. The Best Circuit Breakers (A 2024 Guide)

    See It. Product Specs . Current rating: 20 amp (A) Voltage: 120/240 volt (V) Interrupting capacity: 10 kiloamp (kA) (10,000A) Pros. High-quality device from one of the world's best-known ...

  18. What can be checked with trip-free operation of circuit breaker?

    Trip-free (Close-Open) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection relay system detects the short circuit and trips the breaker.

  19. What is a Trip Curve? Understanding Circuit Breaker Trip ...

    https://www.AutomationDirect.com/circuit-protection - (VID-CP-0009) Circuit breaker and fuse trip curves (CB Trip curves) explain how a trip occurs based on ...

  20. Standard tripping schemes and trip circuit supervision schemes ...

    These schemes are the frequently used and are provided in most medium voltage switchgear applications. 1. General - Functional Requirements. A protection relay is usually required to trip a circuit breaker (CB). The power required by the trip coil of the CB may range from 50 W for a small distribution CB to 3000 W for a large EHV CB.

  21. Trip-free Definition & Meaning

    trip-free: [adjective] free to trip on the occurrence of any condition (as an overload) for which provision is made even if the normal operating lever or the control-switch closing contact is held in the closed position.

  22. What Causes a Circuit Breaker to Trip?

    A circuit breaker may trip due to three primary reasons: overloads, short circuits, and ground fault surges. Overloads occur when a circuit draws more power than it can handle, usually due to too many appliances operating on the same circuit. Short circuits and ground fault surges happen when a hot wire comes into contact with a neutral wire or ...

  23. Circuit Breaker Trip Curves: What Electrical Control Panel Builders

    The trip curve helps electrical control panel builders understand how a circuit breaker will behave under different fault conditions, such as overloads or short circuits. By matching the trip curve with the characteristics of the application, electrical control panel builders can select the correct size and type of circuit breaker, with minimal ...

  24. What Does a Circuit Breaker Tripping Mean?

    The breaker, working in tandem with a fuse, serves as an electrical unit's internal sensing mechanism. At the slightest sense of excess current, the circuit breaker will "trip," triggering a cease in all electrical activity within the circuit. Not only can such a smart mechanism help with preventing damage to wires and other electrical ...